![Weishaupt WG20-/1-C LN Series Manual Download Page 15](http://html.mh-extra.com/html/weishaupt/wg20-1-c-ln-series/wg20-1-c-ln-series_manual_953381015.webp)
Installation and operating instruction
Gas burner WG20…/1-C LN
3 Product description
83240802 1/2020-01 La
15-96
W-FM 05
P11
B4
P
P
B15
L
T1 T2
F2
N
L N
K33
6
B31
P
12
2
M
1
M1
3
B10
P
11
T1
4
K32
5
B1
13
T
I
T
V
T
VZ
T
NZ
T
S
T
N
B1
Ionisation electrode
T
I
Initialisation time: 1 s
B10
Air pressure switch
T
N
Post-purge time: 1.2 s
B15
Temperature or pressure regulator
T
NZ
Post-purge time: 2.4 s
B31
Low gas pressure switch
T
V
Pre-purge time: 21.5 s
F2
Temperature or pressure limiter
T
S
Safety time: 2.7 s
K32
double gas valve
T
VZ
Pre-ignition time: 1.9 s
K33
External valve LPG
Voltage is applied
M1
Burner motor
Flame signal present
P11
Control lamp operation (optional)
Current path
T1
Ignition unit
Start (orange)
Ignition phase (flashing orange)
Burner operation (green)