Installation and operating instruction 

 

Communication module WCM-COM 1.0 home 

83279302 

 2/2012-12

Summary of Contents for WCM-COM 1.0 home

Page 1: ...Installation and operating instruction Communication module WCM COM 1 0 home 83279302 2 2012 12 ...

Page 2: ......

Page 3: ... 8 3 4 Applications 9 3 5 Included in delivery 9 4 Installation 10 4 1 Wall mounting the WCM COM 10 5 Electrical installation 11 5 1 Open housing cover 11 5 2 Connect WCM COM 11 5 3 Connect WCM COM to condensing boiler 13 5 4 microSD card 13 5 5 Network socket 14 5 6 WCM COM connection diagram 14 5 6 1 Mains voltage section 14 5 6 2 Low voltage section 14 5 6 3 Ports for cards on the right of the ...

Page 4: ...7 4 3 WCM KA cascade manager 22 7 4 4 Heating circuits WCM FS and WCM EM 22 7 5 WCM COM settings 23 7 5 1 Network settings 23 7 5 2 Addresses 23 7 5 3 Email Server 24 7 5 4 Error history 24 7 5 5 Messages 24 7 5 6 Monitoring 25 7 5 7 Data Logger 25 7 5 8 Graphic 26 7 5 9 User management 27 7 5 10 Reset 28 7 5 11 Firmware Update 29 8 Authorisation levels of websites 30 ...

Page 5: ...ange 1 1 2 Target group These installation and operating instructions are intended for the operator and qualified personnel They should be observed by all personnel working on the unit Work on the unit must only be carried out by personnel who have the relevant training and instruction Persons with limited physical sensory or mental capability may only work on the unit if they are supervised or ha...

Page 6: ...gnalling and consumption data collection from a heating system 2 2 Safety measures Safety relevant defects must be rectified immediately 2 3 Electrical connection For all work carried out on live parts Observe the accident prevention instruction BGV A3 and adhere to local directives Use tool in accordance with EN 60900 2 4 Disposal Dispose of all materials used in a safe and environmentally friend...

Page 7: ...lowing functionality Network interface 3 2 Technical data 3 2 1 Approval data Basic standards EN 60730 1 EN 60730 2 9 3 2 2 Electrical data Mains voltage Tolerance 230 V 15 10 Mains frequency 50 60 Hz Max consumption 8W Type of protection IP 31 Protection class I 3 2 3 Ambient conditions Temperature during operation 0 C 50 C Temperature during transport storage 30 C 70 C Relative humidity max 80 n...

Page 8: ...le WCM COM 1 0 home 3 Product description 83279302 2 2012 12 Mot 8 32 3 3 Specifications of data connections 3 3 1 eBUS Description Terminal 2 pole eBUS and eBUS Address Automatic 3 3 2 Ethernet Description Connection socket RJ45 Auto MDIX Max speed 100 Mbit s ...

Page 9: ...0 WTC GB 90 300 WTC OW 15 WTC OB 20 35 WCM CPU Step 3 from Version 3 1f WCM CPU Step 4 from Version 4 2e WCM CPU Step 5 from Version 2 2 with CUI 2 3 WCM FS 1 0 und 2 0 WCM EM from 2 0 WCM KA from 2 0 WCM SOL 1 0 home 3 5 Included in delivery The following items are components parts of the delivery Communication module WCM COM 1 0 home SD card plugged in and pre configured Network cable RJ45 Fixin...

Page 10: ...02 2 2012 12 Mot 10 32 4 Installation 4 1 Wall mounting the WCM COM Fit DIN rail 35 mm to wall using fixing material Leave right side of housing accessible for external connections network cables Insert locking contact c Fit communication module to DIN rail Connect cables see CH 5 close housing cover ...

Page 11: ... 5 Electrical installation 5 1 Open housing cover Slightly depress tab and turn screwdriver clockwise Remove housing cover 5 2 Connect WCM COM MM1 N MM1 MFA1 L N 230V L N MFA1 H1 H1 N L MM1 N MM1 MFA1 L N 230V L N MFA1 H1 H1 N L MM1 N MM1 MFA1 L N 230V L N MFA1 H1 H1 N L MM1 N MM1 MFA1 L N 230V L N MFA1 H1 H1 N L 230V L N MFA1 H1 L ...

Page 12: ...ing instructions Communication module WCM COM 1 0 home 5 Electrical installation 83279302 2 2012 12 Mot 12 32 Screened cables The cables for eBUS and M Bus should be connected to the screening shield Cable type LIYCY 2 x 0 75 ...

Page 13: ... terminal 2 of the condensing boiler Several additional modules If more than 2 modules are required Connect condensing boiler and extension and or communication modules via external isolating switch 5 4 microSD card The microSD card is included in delivery and already inserted and programmed with the data required The coded data stored can only be used with the WCM COM The WCM COM has only limited...

Page 14: ...ally Open the bottom of the three covers on the side Plug in network cable 5 6 WCM COM connection diagram 5 6 1 Mains voltage section Terminal Connection Explanation 230 V Supply voltage 230 V 50 Hz PE terminal Protective conductor 5 6 2 Low voltage section Terminal Connection Explanation eBUS Connect 2 pole eBUS cable observe polarity Non power supplying eBUS participant without Sync Generator CA...

Page 15: ...the connection area Terminal Connection Explanation microSD Card already inserted and preconfigured Only limited functionality without SD card Reset key Press for approx 10 seconds until mains LED flashes Resets WCM COM to factory settings 5 6 4 Specific connection area right side of housing Terminal Connection Explanation RJ45 Socket Network cable RJ45 up to 100 Mbit s ...

Page 16: ...onnection between Laptop and WCM COM using the network cable provided 9 The PC recognises the new network connection The network address is obtained within approx 60 seconds and a connection is made 9 This is a connection with limited or no connectivity possibly indicated by yellow warning sign at the connection icon in the taskbar which is correct for operation with WCM COM This connection serves...

Page 17: ...y Enable Obtain IP address automatically 9 Generally Enable DNS Server Address automatically 9 Alternative configuration Enable Automatically assigned private IP address Measures if website is not displayed If in spite of a network connection to the WCM COM the start page of the browser Internet Explorer 8 is not displayed the connection settings in the browser must be checked File 9 Offline opera...

Page 18: ...ermanent connection to the Internet Router configuration to permit access to the WCM COM 9 The system is accessible via the Internet by entering the public IP address into the address line of the browsers The IP addresses of private Internet connections are usually changed daily A dynamic Domain Name System DNS is recommended to allow the WCM COM to be addressed On the one hand this provides an in...

Page 19: ...hase of WCM COM the Bus scan takes approx 3 minutes If no eBUS participants are detected the Bus scan continues permanently 7 2 User interface Each of the three possible ways of communication leads to a uniform and identical user interface A current web browser e g Internet Explorer Apple Safari Mozilla Firefox is required as software on the PC 7 2 1 System prerequisites The computer used must mee...

Page 20: ... The following table shows the different components of the operation Display in browser Microsoft Internet Explorer 8 Explanation Checkbox for status display cannot be edited Checkbox for selecting several options can be edited Checkbox to select one option can be edited Display of current process value cannot be edited Display of last process value Failed to read cannot be edited Display of param...

Page 21: ... a number of different heat exchangers and controllers of the WCM system see Ch 3 4 Various temperatures process values or error messages are monitored checked and if necessary reported on Detailed descriptions can be found in the relevant installation and operating manuals WTC WCM FS WCM EM WCM KA 7 4 1 WTC heat exchanger Current temperatures status and process variables are shown in the sub menu...

Page 22: ...stem configuration parameters from an associated WCM EM are also displayed Transmit settings carried out using button Apply 9 If limit values are ignored an adjustment will be made in the controller this correction will be displayed during the next automatic readout For the engineer selected parameters which can be edited are displayed on an additional page It is possible to assign the heating cir...

Page 23: ... 6 9 The MAC address is the unique identification address of the WCM COM in networks For integration into existing local networks the activation of the device using its MAC address may be required This is factory assigned to the device and cannot be changed The changed settings concerning the network will only take effect after a restart of the WCM COM 7 5 2 Addresses System The WCM COM has specif...

Page 24: ...tem time of the relevant time master WCM FS or WCM KA If the system does not have a master the timer begins at start up at 01 01 2000 00 00 hrs Message type Error Error in heating system WTC or control device L Limit of monitoring exceeded Error code Error Interpretation with the aid of the installation and operating manual L Limit Ten Number of monitoring 1 8 One 1 Lower limit violated 2 Upper li...

Page 25: ...at any time Previously recorded data is therefore lost when restarting The data can be backed up by downloading completed records 9 The status yellow active grey inactive is shown Start Stop of monitoring by pressing the button The selection is made on the relevant page of the process values by ticking the relevant checkboxes in column DataLog 9 Only possible with type of operation Stop of the Dat...

Page 26: ...ther processing it with Microsoft Excel The following restriction result the representation of the Graphic is not affected Recording cycle Maximum duration 10 seconds approx 1 week 1 minute approx 6 weeks 10 minutes approx 1 year The Controls buttons allow skipping within the recording section The increments from page forward or page back is equal to 250 recording points It is also possible to ski...

Page 27: ...ger possible Engineer As engineer the user has access to all adjustable parameters of the heating system connected Adjustment and parameter settings can therefore be carried out in the authorisation level Engineer User For the User rights are limited to viewing process values or to carry out user relevant settings room temperature settings type of operation time programs etc for the heating circui...

Page 28: ...version for other applications in the same scope is generated Restart The WCM COM is restarted Reset The WCM COM is reset to factory settings If this is executed remotely via a manually configured network the WCM COM looses all settings and must be reconfigured via direct connection 9 If the configuration is incorrect or if the system is changed etc all parameters are reset to a defined condition ...

Page 29: ... 10 Please do not close or navigate through the browser during the upload of the fwu file wait until the message Firmware successfully uploaded unit will restart or one of the status messages listed below is displayed Firmware Update Status The WCM COM can display various messages to show the current status Firmware successfully uploaded unit will restart The file has been successfully transferred...

Page 30: ...ss values User WTC Engineer Engineer WCM KA process values User WCM KA Engineer Engineer Heating circuits Process values User User User Date Time User Engineer Engineer Configuration User Time programs User WCM COM Network settings Admin Addresses Admin Email Server Admin Error history Engineer Messages Engineer Monitoring Engineer Data Logger Engineer Graphic Engineer User management Admin Reset ...

Page 31: ...dress 18 23 IPv4 17 J Java Plugin 26 L LED 19 Liability 5 Limited connectivity 16 Low voltage 14 M MAC Address 23 Mains voltage 7 14 M Bus 12 Messages 24 microSD card 13 15 Monitor 22 25 Monitoring 25 N Network 16 23 Network connection 17 Network socket 14 O Operating display 19 Operation 19 P Password 21 POP3 24 Protection Class 7 Protective conductor 14 Proxy Server 17 R Regulations 6 Reset 19 2...

Page 32: ...r environmentally friendly heating Fuel Gas or oil as desired Thermo Condens The innovative condensing boilers with the SCOT system Efficient low in emissions versatile Ideal for domestic heating Floor standing gas condensing boiler with ratings of up to 1200 kW cascade for higher heat demands Heat pumps The heat pump programme offers solutions for utilisation of heat from air soil and ground wate...