Weir SPM Operating And Maintenance Instructions Manual Download Page 7

VIII.  Setting and Adjusting 
Pressure:

The unloading valve is direct acting.  The pressure set on 
the nitrogen regulator is directly related to the relief 
pressure.  The higher the nitrogen pressure, the higher the 
relief set point.  Clean dry air at a minimum of 1,200 psi 
(6,000 psi max) may also be used.

Use the following procedure to obtain the correct set point.  
A few attempts at working pressure may be required to 
confirm the set point (Chart 1).

CAUTION:
Bleed off all air from the fluid system.  Trapped air 
will become energized and may cause injury to 
personnel when the valve relieves.

1. Screw the pressure regulator  8  adjustment screw all the
    way out (Counter Clockwise, Fig 4).

CAUTION:
When the handle hits its stop, the top of the 
regulator may start to unscrew.  Do not unscrew 
the regulator top any further.  Failure to comply 
may cause injury to personnel when pressure is 
applied to the valve.

2. Open the valve  20  on the nitrogen bottle or from the air
    source.  The inlet gauge  6  on the regulator  8  should
     indicate the pressure in the nitrogen bottle.

3. Tighten the backpressure regulator  9  adjustment screw
    fully (Clockwise).

    predicted gas pressure does not produce the desired set
    pressure, you may have to adjust the regulator  8  up or
    down.

   Some of the factors affecting performance include
   ambient and liquid temperature, and gas media used (air
   vs nitrogen).

9. Reset the nitrogen pressure to the new setpoint and 
    repeat items 3, 4, 5 of this section.  Test the line again
    until the valve relieves. 

NOTE:
Once the relief valve is adjusted to the correct set 
point it is normal for the gas pressure to rise as 
fluid in the line  19  approaches the set pressure. 
The backpressure regulator will vent gas to 
compensate this increase in gas pressure.  It is also 
normal for the valve to release (unload) liquid at a 
lower fluid pressure than when it first opened.  The 
set pressure should, however, return to the setpoint 
fairly rapidly once the liquid pressure has decayed.

CAUTION:
Never block the valve discharge line.  It will cause 
valve damage.

7

4. Turn the adjustment screw on the regulator  8  until the
    gas line pressure reaches a nominal set point.  Use the
    Chart 1 to find gas pressure versus "set" pressure.

5. Turn the adjustment screw on the backpressure 
    regulator  9  counter clockwise until the gas starts to
    exhaust (gas begins to make a sound).  Then slightly turn
    the adjustment screw clockwise until the backpressure
    regulator just stops exhausting gas.

NOTE:
Always set the pressure in the Rising Direction.  If 
you pass a set point drop the pressure to about 50 
psi below the set point then re-approach the set 
point.

6. Test the working pressure by slowly raising the line
    (liquid) pressure until the valve begins to relieve.  The
    treating line pressure should stabilize and stop rising once
    this happens.

7. Reduce the line pressure until the cylinder rod  4   and
    wear  14  sleeve are fully seated.

8. The relationship between gas pressure and line (liquid)
    pressure is defined by Chart 1.  These values are from
    actual tests using water as the liquid.  However, values in
    this chart should be considered preliminary and if the

Line Set

Pressure PSI

1000
1500
2000
2500
3000
3500
4000
4500
5000
5500
6000
6500
7000
7500
8000
8500
9000
9500

10000
10500
11000
11500
12000
12500
13000
13500
14000
14500
15000

Required Nitrogen

(or gas) PSI

37
55
73
91

109
127
145
163
181
199
217
235
253
271
288
306
324
342
360
378
396
414
432
450
468
486
504
522
540

Chart. 1

Summary of Contents for SPM

Page 1: ...rovided without the prior written consent of the copyright owner SPM SAFETY IRON SAFETY HAMMER SUR DROP DESTINY STAMPEDE VERIBAND DURALAST and GLADIATOR are trademarks and or registered trademarks of S P M Flow Control Inc WEIR is a trademark and or registered trademark of Weir Engineering Services Limited Certain features of some of the products disclosed in this document may be protected worldwi...

Page 2: ...T END NSCWP PSI SERVICE SEALS TEMP RANGE Gas Side Specifications Low Pressure Working Range 0 to 800 psi Recommended Nitrogen Bottle 2 000 psi Recommended Rupture Disc 2 250 psi Bottle or source gas pressure should be twice maximum low pressure working range Operating Temperature 22 F to 120 F 30 C to 49 C Weir SPM s 3 Emergency Unloading Valve is available with Weir SPM Wing Union Connections The...

Page 3: ...sonnel or equipment SPM highly recommends that an isolator valve be placed between the pressure line and the Relief Valve separate series of H2S service unloading valve CAUTION Weir SPM s 3 standard service Emergency Unloading Valve is not intended for use in the sour gas environment DO NOT USE FOR H2S SERVICE Weir SPM does offer a separate series of H2S service unloading valve Contact your Weir S...

Page 4: ...Brass 7 600 Grit Sandpaper 8 Anti seize Lubrication 9 Hand and Eye Protection DISASSEMBLY Fig 4 5 MAKE SURE THAT THERE IS NO PRESSURE ON THE VALVE 1 If the nitrogen cylinder 2 is attached close the high pressure cylinder valve 20 Then bleed down and remove the nitrogen line 19 and vent line from Figure 2 if so equipped from the unloading valve 1 Fig 4 2 Secure the valve in a horizontal position by...

Page 5: ...7 Cartridge 10 Inspect the seal 29 surface where the cartridge fits against the body 2 Inspect the seal surface where the main seal assembly 5 fits If these surfaces have deteriorated the cartridge should be replaced FIG 4 FIG 5 Ref No FIG 5 Part No Complete Internal Parts Kit 4L23547 5 3A23356 10 3P23295 11 3P23297 12 3P23298 14 3P23308 16 3P23330 17 4P10258 20 P16637 22 P20006 24 P23302 25 P2330...

Page 6: ... over seal 22 with backup ring 24 onto cylinder rod 4 Attach rod cap with 1 4 socket screws 30 Safety wire socket screws 3 Install sleeve 11 over seal 28 onto rod 4 Install piston 8 over seal 28 onto rod 4 Attach jam nuts 23 to rod 4 with blue thread lock Install seal 25 onto piston 8 4 Install seals 26 31 27 20 into flange 1 5 Install rod and piston assembly into flange 1 Install entire package i...

Page 7: ...st the line again until the valve relieves NOTE Once the relief valve is adjusted to the correct set point it is normal for the gas pressure to rise as fluid in the line 19 approaches the set pressure The backpressure regulator will vent gas to compensate this increase in gas pressure It is also normal for the valve to release unload liquid at a lower fluid pressure than when it first opened The s...

Page 8: ...d discharge nozzle or wear sleeve d Damaged high pressure cylinder connection e Contaminants trapped between wear sleeve and nozzle or main seal a Damaged inner or outer or both flange seals a Valve set incorrectly a Use only as an emergency unloading device b Install sufficient quantity of valves to meet capacity requirements a Raise set pressure slightly a Set valve correctly b Replace damaged p...

Page 9: ... READ THIS OPERATING AND MAINTENANCE INSTRUCTIONS MANUAL BEFORE OPERATING PRODUCT IT IS THE RESPONSIBILITY OF THE EMPLOYER TO PLACE THE INFORMATION IN THIS MANUAL INTO THE HANDS OF THE OPERATOR FAILURE TO READ UNDERSTAND AND FOLLOW THE OPERATING AND MAINTENANCE INSTRUCTIONS MANUAL COULD RESULT IN SEVERE PERSONAL INJURY OR DEATH WARNING 2011 Weir SPM V 1 02 11 9 ...

Reviews: