background image

2

 

Particular note should be taken to the position of variable speed drives and switching power supplies. 

Their input and load cables should be screened to a central star earth point. 

 
 

2.1.2 Making a NEMA-4 Mounting 

Panel   
Details
 

The unit can be mounted into panels with a depth of 4”(105mm).    It is recommended that 
the unit be mounted on the front panel of a steel enclosure, through an appropriate 
opening*. Allow a clearance of 1”(25mm) around the sides of the unit for mounting 
hardware. Allow clearance for cable connections to the back of the unit. Unit depth may 
vary according to cable type used. Typically, plan a depth to accommodate at least 
4”(105mm) behind the panel. 

NEMA-4 
Mounting
 

Put the unit through the panel cut out. Slide the clamps into the 6~8 holes provided around 
the case. Tighten the clamping screws in an even pattern until the unit is secured in the 
panel. 

Caution! 

Do not over tighten mounting clamps! 

Note: 

Specifications 

Note: To seal to NEMA-4 specifications, all supplied mounting clamps must be used and 
panel cannot flex more than 0.010”. 

2.1.3 Environmental Considerations 

 

 

The NP-610p are to be used indoors as built in displays. Make sure that the displays are 
installed correctly and that the operating limits are followed (See Specifications). 

 

Do not operate the unit in areas subject to explosion hazards due to flammable gases, 
vapors or dusts. 

 

The unit should not be installed where fast temperature variations and/or high humidity 
are present. This will cause condensation of water in the device. 

 

Do not install these terminals in environments where have inflammable gases. 

 

2.2 Power Connections 

Make sure that all local and national electrical standards are met when the installing the unit. 
Contact your local authorities to determine which codes apply. 

2.2.1 Power Requirements 

 

 

Power 

The NP-610p can be powered by DC power only. The specified voltage 
range is 

24±20%

 Volts DC. This insures compatibility with most controller 

DC systems.   

The power conditioning circuitry inside the unit is accomplished by a 
switching power supply. The peak starting current can be as high as 700mA. 

 

Fusing 
Requirements
 

If the display does not come on within 2 seconds of power up, remove 
power. An internal fuse will prevent damage if the polarity of the DC power 
is incorrect. Check wiring to insure proper connections and try to power up 
again. 

 

Caution 
High Voltage

 

An Internal fuse will prevent damage for over voltage condition however it 
isn’t guaranteed. 

DC voltage sources should provide proper isolation from main AC power 
and similar hazards. 

 

Summary of Contents for NP-610p Series

Page 1: ...the panel during wash downs Electrical Environment The NP 610p Series has been tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Proper wire routing and grounding will insure proper operation Mechanical Environment Avoid installing units in environments where sever...

Page 2: ... are installed correctly and that the operating limits are followed See Specifications Do not operate the unit in areas subject to explosion hazards due to flammable gases vapors or dusts The unit should not be installed where fast temperature variations and or high humidity are present This will cause condensation of water in the device Do not install these terminals in environments where have in...

Page 3: ...al 2 2 2 Grounding Requirements Chassis ground must be used DC ground is not directly coupled to Earth ground internally It is preferable not to ground DC negative return to chassis ground as poor site earths can introduce noise into a system but if necessary an earth connection should be made from the power supply return point to the central star earth point Ground conductors should be as short a...

Page 4: ...ation consideration should be given to the use of locks or other means of assuring that only authorized personnel can make such changes These recommendations are intended as safeguards against the failure of critical components and the effects of such failures or the inadvertent errors that might be introduced if programs are changed while the equipment is in operation The ICS 3 304 81 Safety Reco...

Page 5: ...M3 RS 232 Port Pin Symbol Com1 RS485 2w Com1 RS485 4w Com3 RS485 CAN Bus 1 Rx Data Rx 2 Rx Data Rx 3 Tx Tx 4 Tx Tx 5 GND Signal Ground 6 Data Data 7 Can_L Can_L 8 Can_H Can_H 9 Data Data 2 3 3 USB Host port Support various devices with USB interface such as mouse keyboard USB stick printer etc 2 3 4 Connecter Wire NP 610p Ethernet NP 610p Ethernet RJ45 Wire color 1 TX White Orange 2 TX Orange 3 RX...

Page 6: ...efault password is 111111 However other passwords including download and upload password have to be reset Note When the reset action is be taken projects and saved data in the HMI will all be cleared 2 4 CE Requirements EU directives that apply to the NP 610p Series EMC Directive 89 336 EEC 92 31 EEC 93 68 EEC electromagnetic emissions and immunity Machinery Directive 89 392 EEC 91 368 EEC 93 44 E...

Page 7: ...e T USB USB Host port x 1 USB Client port x 1 Processor 32bit RISC CPU 600MHz RAM 128MB Flash memory 128MB SD SDHC card slot Yes RTC Built in General Specification Input Power 24 20 VDC Max Power Consumption 400 mA 24VDC Power Isolation Inside Protection structure NEMA 4 IP65 front panel O ring seal Operating Temperature 0 50 C Operation humidity 10 90 RH non condense Enclosure Plastic Dimensions ...

Page 8: ...intek the product fails due to damage from shipment handling storage accident natural and man mad b if the product fails due to misuse including but not limit to incorrect set up and wiring current leakage from machine platform and incorrect input power c if the product has been maintained in a manner not conforming to product s instructions or has been modified in any way d if the serial number h...

Page 9: ...9 4 0 Dimensions of NP 610p Cutout dimensions ...

Reviews: