background image

 

 

EasyBuilder Pro Software Settings 

Launch EasyBuilder Pro software, select your project file, press F7 shortcut key to open the download 
dialog box:   
Select Ethernet > IP tab > Enter your HMI IP > Click Download to download this project file to HMI. 
Using screensaver and backlight saver is recommended in order to avoid image persistence caused 
by displaying the same image on HMI for a long time. 
( Please refer to EasyBuilder Pro User Manual for software operation details ) 
 

Communication Connections 

NOTE:

   

1. 

COM2 and COM3 [RS485] 2W support MPI 187.5K, please use one at a time. 
 

          COM1 RS232, 9 Pin, Male, D-sub   

 

  COM2/3 RS485, 9 Pin, Female, D-sub 

 

 

 

 

 

 

 

 

DIP SW Settings 

 

 

 

 

Battery Replacement

 

Battery replacement shall be performed by qualified personnel only and care must be taken when 
handling lithium batteries. For more information on battery replacement and disposal considerations, 
please refer to the following link

http://www.weintek.com/download/MT8000/eng/FAQ/FAQ_103_Replace_Battery_en.pdf

 

Limited Warranty                                                                                                         

 

This product is limited warranted against defects in design and manufacture. 

The proven defective product will either be repaired or replaced, at Weintek’s discretion.   

This warranty shall not cover any product which is   

(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products. 
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.   
(c) Product has been repaired or taken apart by unauthorized technicians.   
(d) Products whose identification markings have been removed or damaged.

 

 

SW1 

SW2 

SW3 

SW4 

Mode 

ON 

OFF 

OFF 

OFF

 

Touch Screen Calibration Mode 

OFF 

ON 

OFF 

OFF

 

Hide HMI System Setting Bar 

OFF 

OFF 

ON 

OFF

 

Boot Loader Mode 

OFF 

OFF 

OFF 

ON 

Not supported 

OFF 

OFF 

OFF 

OFF

 

Normal 

Another method to enter touch screen calibration mode: Press and hold 
anywhere on the screen for more than 2 seconds when HMI starts. 

CAUTION

NN

 

 

NOTE:   

Make sure that all local and national electrical standards are met when installing 
the unit. Contact your local authorities to determine which codes apply. 

PIN# 

COM1 [RS232] 

 

RxD 

TxD 

 

GND 

 

RTS 

CTS 

 

 

PIN# 

COM2 [RS485] 

COM3 

[RS485] 

2W 

4W 

Data- 

Rx- 

 

Data+ 

Rx+ 

 

 

Tx- 

 

 

Tx+ 

 

GND 

 

 

Data- 

 

 

 

 

 

 

 

 

Data+ 

 

Power 

The 

unit

 can be powered by DC power only, voltage range: 24±20% Volts DC, compatible with 

most controller DC systems. The power conditioning circuitry inside the unit is accomplished by a 

switching power supply. The peak starting current can be as high as 2A.

 

Fusing 
Require- 
ments 

If the display does not come on within 5 seconds of power up, remove power. An internal fuse will 

prevent damage if the polarity of the DC power is incorrect. Check wiring for proper connections 

and try to power up again. 

High 
Voltage 

An Internal fuse will prevent damage for overcurrent 

condition however it isn’t guaranteed. DC 

voltage sources should provide proper isolation from main AC power and similar hazards. 

Emergency 
Stop 

A Hard-wired EMERGENCY STOP should be fitted in any system using 

HMI

 to comply with ICS 

Safety Recommendations. 

Supply 
Voltage 
Condition 

Do not power the 

unit

 and inductive DC loads, or input circuitry to the controller, with the same 

power supply. Note: The 24 VDC output from some controllers may not have enough current to 

power the 

unit.

 

Wire 
Routing 

a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded). 

b. Please use twisted pair cables for power wire and signal wire and conform to the impedance 

matching. 

c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression devices. 

d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires. 

e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power 

supply and the frame ground. This provides a path for static and high frequency dissipation. 

Typical values to use are 1M Ohm and 4700pF. 

 

 

 

CAUTION 

NOTE: 

Make sure that all local and national electrical standards are met when 

installing the unit. Contact your local authorities to determine which codes apply. 

Hardware 
Considerations 

The system designer should be aware that devices in Controller systems could fail and thereby 

create an unsafe condition. Furthermore, electrical interference in an operator interface can lead to 

equipment start-up, which could result in property damage and/or physical injury to the operator. 

If you use any programmable control systems that require an operator, be aware that this potential 

safety hazard exists and take appropriate precautions. Although the specific design steps depend on 

your particular application, the following precautions generally apply to installation of solid-state 

programmable control devices, and conform to the guidelines for installation of Controllers 

recommended in NEMA ICS 3-304 Control Standards.

 

Programming 
Considerations 

To conform with ICS Safety Recommendations, checks should be placed in the controller to ensure 

that all writable registers that control critical parts of plant or machinery have limit checks built into 

the program, with an out-of-limit safe shut down procedure to ensure safety of personnel. 

GME8071ER_MT8071iER1_Installation_170620 

 

 

 

 

 

 

 

 

DANGER 

Reviews: