9

2.1.2 Making a NEMA-4 Mounting 

Panel  
Details

 

The unit can be mounted into panels with a depth of 4”(105mm).    It is recommended that 
the unit be mounted on the front panel of a steel enclosure, through an appropriate 
opening*. Allow a clearance of 1”(25mm) around the sides of the unit for mounting 
hardware. Allow clearance for cable connections to the back of the unit. Unit depth may 
vary according to cable type used. Typically, plan a depth to accommodate at least 
4”(105mm) behind the panel. 

NEMA-4 
Mounting

 

Put the unit through the panel cut out. Slide the clamps (packed with product) into the 5 
holes provided around the case. Tighten the clamping screws in an even pattern until the 
unit is secured in the panel. Screw Torque: 2.6~3.5 lbf.in. (For reaching waterproof effect 
and to prevent the panel from being deformed.) 

VESA 
Mounting 

There are 4 holes on back panel for locking VESA, The screw: M4 P0.7mm, length: 
shorter then 8.0mm, and screw torque: 2.6 lbf.in. 

Caution!

 

Do not over tighten mounting clamps! 

Note:

 

57

Specifications 

Note: To seal to NEMA-4 specifications, all supplied mounting clamps must be used and 
panel cannot flex more than 0.010”. 

10

2.1.3 Environmental Considerations 

 

z

 

The MT-600/8000 are to be used indoors as built in displays. Make sure that the displays 
are installed correctly and that the operating limits are followed (See Specifications). 

z

 

Do not operate the unit in areas subject to explosion hazards due to flammable gases, 
vapors or dusts. 

z

 

The unit should not be installed where fast temperature variations and/or high humidity 
are present. This will cause condensation of water in the device. 

z

 

Do not install these terminals in environments where have inflammable gases. 

 

5

2.2 Power Connections 

Make sure that all local and national electrical standards are met when the installing the unit. 
Contact your local authorities to determine which codes apply. 

11

2.2.1 Power Requirements 

2

 

 

Power

 

The MT-600/8000 can be powered by DC power only. The specified 
voltage range is 24

±

20% Volts DC.    This insures compatibility with most 

controller DC systems.   
The power conditioning circuitry inside the unit is accomplished by a 
switching power supply. The peak starting current can be as high as 2A. 

 

Fusing 
Requirements

 

If the display does not come on within 5 seconds of power up, remove 
power. An internal fuse will prevent damage if the polarity of the DC 
power is incorrect. Check wiring to insure proper connections and try to 
power up again. 

 

51

Caution 

50

High Voltage

 

An Internal fuse will prevent damage for over voltage condition however 
it isn’t guaranteed. 
DC voltage sources should provide proper isolation from main AC power 
and similar hazards. 

 

Caution 
Emergency 
Stop

 

A Hard-wired EMERGENCY STOP should be fitted in any system using 
an MT-600/8000 to comply with ICS Safety Recommendations. 

 

52

Supply Voltage 

Caution 

53

Condition 

Do not power the MT-600/8000 and inductive DC loads, or input circuitry 
to the controller, with the same power supply. Note: The 24 VDC output 
from some controllers may not have enough current to power the 
MT-600/8000. 

 

Caution  

54

Wire Routing 

Wire lengths should be minimized (Maximum 1600’ (500 m) shielded, 
1000’ (300 m) unshielded). 
Wires should be run in pairs with a neutral or common paired with a hot o
signal line. 

Summary of Contents for MT-8104iH

Page 1: ...has been tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Proper...

Page 2: ...or high humidity are present This will cause condensation of water in the device z Do not install these terminals in environments where have inflammable gases 5 2 2 Power Connections Make sure that al...

Page 3: ...round terminal of the power connector This ground connection should be run directly to the central star earth connection point as recommended in most Installation Instructions 1 4 2 2 4 Safety Guideli...

Page 4: ...s The COM light on the front of the MT 600 8000 will turn on with each Ethernet communication Shielded cable must be used for long lengths or cables run in an electrically noisy environment Do not run...

Page 5: ...MT8070iH MT8100i and MT8104iH 1 Using USB cable mini side plug to HMI and another side plug into PC The PC will display Found New Hardware Wizard dialog Select Install from a list or specific location...

Page 6: ...ries will jump to Touch Adjust Touch screen calibration mode After calibration the pop up window appears as the illustration below Users will be inquired restoring the system password to the default v...

Page 7: ...000 hr min Touch panel 4 wires resistive type Touch Accuracy Active Area Length X 2 Width Y 2 Surface Hardness 4H I O port COM1 RS 232 RS 485 2W 4W COM2 RS232 COM3 RS 232 RS 485 2W Ethernet port 10 1...

Page 8: ...f f COM1 RS232 COM2 RS232 COM3 RS485 COM3 RS232 COM1 RS485 2 4W RESET FUSE GND 24V DIP SW FUSE5X20 g h k i j b 257mm 10 12 199mm 7 83 a Com1 RS485 Com3 RS485 Com3 RS232 g USB Client port b USB Host po...

Reviews: