weintek MT-6070iH3 Series Installation Instruction Download Page 3

3

 

 

Caution 

Emergency 

Stop

 

A Hard-wired EMERGENCY STOP should be fitted in any system using 

an MT6070iH3 to comply with ICS Safety Recommendations. 

 

Caution 

Supply Voltage 

Condition 

Do not power the MT6070IH3 and inductive DC loads

, or input 

circuitry to the controller, with the same power supply. Note: The 24 VDC 

output from some controllers may not have enough current to power the 

MT6070iH3. 

 

Caution  

Wire Routing 

Wire lengths should be minimized (Maximum 1600’ (500 m) shielded, 

1000’ (300 m) unshielded). 

Wires should be run in pairs with a neutral or common paired with a hot or 

signal line. 

If wiring is to be exposed to lightning or surges, use appropriate surge 

suppression devices. 

Keep AC, high energy, and rapidly switching DC wiring separate from 

signal wires. 

Equip ungrounded DC supplies with a resistor and capacitor in parallel to 

earth ground. This provides a path for static and high frequency 

dissipation. Typical values to use are 1MOhm and 4700pF. 

 

Caution  

 

To prevent the HMI from becoming damaged or having sound output 

issues, after turning the device off, please wait 10 seconds before turning 

the device on again. 

 

Connection 

 

To make a connection, strip about 3/8” of insulation off the end of the 

wire, turn the connector screw counterclockwise until the gap is wide 

open, insert the wire all the way in, and turn the screw clockwise until it’s 

tight. 

Connect positive DC line to the ‘+24V’ terminal and the DC ground to the 

‘0V‘ terminal. 

2.2.2 Grounding Requirements 

 

 

Chassis ground must be used.    DC ground is not directly coupled to Earth 

ground internally. It is preferable not to ground DC negative return to chassis 

ground as poor site earths can introduce noise into a system, but if necessary 

an earth connection should be made, from the power supply return point to 

the central star earth point. Ground conductors should be as short and as large 

in size as possible. The conductors must always be large enough to carry the 

maximum short circuit current of the path being considered. Ground 

conductors should be connected to a tree from a central star earth ground 

point. This ensures that no ground conductor carries current from any other 

branch. 

2.2.3 CE Requirements 

To make an MT6070iH3 comply with EMC directives, and to reduce susceptibility to electrical 

interference, a separate #14 AWG ground wire should be taken to the chassis ground terminal of the 
power connector. This ground connection should be run directly to the central star earth connection 
point (as recommended in most Installation Instructions). 

2.2.4 Safety Guidelines 

This section presents recommended installation practices, and procedures. Since no two 

applications are identical, these recommendations should be considered as guidelines. 

 

Hardware 
Considerations 

WARNING! 
The system designer should be aware that devices in Controller systems could 

fail and thereby create an unsafe condition. Furthermore, electrical 

interference in an operator interface, such as a MT6070iH3, can lead to 

equipment start-up, which could result in property damage and/or physical 

injury to the equipment operator. 

If you, or your company, use any programmable control systems that require 
an operator or attendant, you should be aware that this potential safety hazard 

Summary of Contents for MT-6070iH3 Series

Page 1: ...es has been tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Proper wire routing and grounding will insure proper operation Mechanical Environment Avoid installing units in environments where severe mechanical vibration or shocks are present 2 0 Installation Instr...

Page 2: ... z The MT6070iH3 are to be used indoors as built in displays Make sure that the displays are installed correctly and that the operating limits are followed See Specifications z Do not operate the unit in areas subject to explosion hazards due to flammable gases vapors or dusts z The unit should not be installed where fast temperature variations and or high humidity are present This will cause cond...

Page 3: ...ot directly coupled to Earth ground internally It is preferable not to ground DC negative return to chassis ground as poor site earths can introduce noise into a system but if necessary an earth connection should be made from the power supply return point to the central star earth point Ground conductors should be as short and as large in size as possible The conductors must always be large enough...

Page 4: ...only authorized personnel can make such changes These recommendations are intended as safeguards against the failure of critical components and the effects of such failures or the inadvertent errors that might be introduced if programs are changed while the equipment is in operation z The ICS 3 304 81 Safety Recommendations are reproduced by permission of the National Electrical Manufacturers Asso...

Page 5: ...rnal device 2 3 4 USB Client port Mini USB cable RZCMT6100 is used to download projects from PC by the USB 2 0 client port Support USB 2 0 client interface The cable regulation must accord with HI SPEED USB Revision 2 0 SHIELDED Note Please do not connect HMI with PLC and PC simultaneously to prevent potential difference from destroying USB ports of HMI and PC How to install USB driver of HMI i se...

Page 6: ...d 4 to ON position the rest of Dips remain on OFF position and then reboot MT6070iH3 Under this situation MT6070iH3 will jump to Touch Adjust Touch screen calibration mode After calibration the pop up window appears as the illustration below Users will be inquired if restoring the system password to the default value z When YES is chosen another pop up dialog appears as below Users will be confirm...

Page 7: ... 2001 A2 2003 3 0 Specifications MT6070iH3 Hardware Specification Display 7 TFT LCD Brightness 350 cd m2 Color 65 536 colors Contrast Ratio 500 1 Resolution WxH dots 800 x 480 Back light LED Backlight life time avg 30 000 hr min Touch panel 4 wires resistive type Touch Accuracy Active Area Length X 2 Width Y 2 I O port COM1 RS 232 RS 485 2W 4W COM2 RS232 COM3 RS 232 RS 485 2W Ethernet port N A USB...

Page 8: ... product has been maintained in a manner not conforming to product s instructions or has been modified in any way d If the serial number has been defaced or removed 4 0 Dimensions of MT 6070iH3 GME6070I1_MT6070iH3_Installation_120409 a DIP SW Reset button e Com1 RS485 Com3 RS485 Com3 RS232 b Fuse f Com1 RS232 Com2 RS232 c Power connector g USB Host port d VESA 75mm screw holes h USB Client port CO...

Reviews: