Installation Instruction 

 

 
1.0 Installation and Startup Guide   

Install Environment 

 

Where  
Used

 

The MT-600/8000 Series is designed for industrial. The temperature range of operating 
is from 32 to 122 °F (0 to 50 °C), as majority of industrial environments. It may not be 
suitable for using in certain outdoor applications. Please consult the factory for 
advised usage in outdoor applications. 

NEMA 

Rating 

 

The MT-600/8000 Series front bezel is NEMA 4 rated. When installed properly in a 
NEMA 4 panel, the NEMA 4 rating of the panel will not be compromised. This means 
that fluids will not enter the panel during wash downs. 

Electrical 

Environment 

The MT-600/8000 Series has been tested to conform to European CE requirements. 
This means that the circuitry is designed to resist the effects of electrical noise. This 
does not guarantee noise immunity in severe cases.    Proper wire routing and 
grounding will insure proper operation. 

Mechanical 

Environment 

 

 

 

 

Avoid installing units in environments where severe mechanical vibration or shocks 
are present. 

 

2.0 Installation Instructions 

2.1 Mounting Instructions 

2.1.1 Location Considerations 

 

Care should be taken when locating equipment behind the unit to ensure that AC power wiring, PLC 

output modules, contactors, starters and relays, and any other source of electrical interference are located 

away from the back of the unit. 

 

Particular note should be taken to the position of variable speed drives and switching power supplies. 

Their input and load cables should be screened to a central star earth point. 

 

 

Summary of Contents for MT-600 series

Page 1: ...ies has been tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Pr...

Page 2: ...The MT 600 8000 are to be used indoors as built in displays Make sure that the displays are installed correctly and that the operating limits are followed See Specifications z Do not operate the unit...

Page 3: ...nal 2 2 2 Grounding Requirements Chassis ground must be used DC ground is not directly coupled to Earth ground internally It is preferable not to ground DC negative return to chassis ground as poor si...

Page 4: ...e the equipment is in operation consideration should be given to the use of locks or other means of assuring that only authorized personnel can make such changes These recommendations are intended as...

Page 5: ...0 SHIELDED Note Please do not connect HMI with PLC and PC simultaneously to prevent potential difference from destroying USB ports of HMI and PC How to install USB driver of HMI i series It is necessa...

Page 6: ...n another pop up dialog appears as below Users will be confirmed again if restoring the system password to the default value and will be asked to input YES Then click OK The default password is 111111...

Page 7: ...ming to product s instructions or has been modified in any way d if the serial number has been defaced or removed 3 0 Specifications MT6056i Hardware Specification Display 5 6 TFT LCD Brightness 300 c...

Page 8: ...ew holes GME6056I1_MT6056i_Installation_120409 COM CPU PWR FUSE5X20 COM3 RS485 COM1 RS232 COM2 RS232 COM1 RS485 2 4W COM3 RS232 SD e MT6056i 192mm 7 56 W x 138mm 5 43 H R2 R0 08 204 8 03 150 5 91 48 7...

Reviews: