Weil-McLain SlimFit 1000 User'S Information Manual Download Page 1

Part number 550-100-181/0517

User’s 

Information Manual

 

If the information in this manual is not followed exactly, a fire or explosion may 

result, causing property damage, personal injury or loss of life.

Do not store or use gasoline or other flammable vapors and  

liquids in the vicinity of this or any other appliance.

— WHAT TO DO IF YOU SMELL GAS —

  Do not try to light any appliance.

•  Do not touch any electrical switch; do not use any telephone in your building.

•  Immediately call your gas supplier from a neighbor’s telephone. Follow the gas supplier’s instructions.

•  If you cannot reach your gas supplier, call the fire department.

•  Installation & service must be performed by a qualified installer, service technician or the gas supplier.

®

Series 2 

Models 1000 - 2000 MBH

Commercial Condensing

Gas-fired water boilers

Summary of Contents for SlimFit 1000

Page 1: ...other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any telephone in your building Immediately call your gas supplier from a nei...

Page 2: ...and service must be performed by a qualified installer service agency or the gas supplier who must read and follow the supplied instructions before installing servicing or removing this boiler This b...

Page 3: ...heatexchangerreducesheattransfer over heatsthemetal andcausesheatexchangerfailure Additionof oxygen can cause internal corrosion in system components Leaksinboilerorpipingmustberepairedatoncetoprevent...

Page 4: ...valve Union Drip leg Boiler gas connection From gas supply External gas piping by installer See next page for location of interior boiler manual gas valve 4 SlimFit Series 2 commercial condensing gas...

Page 5: ...tion right hand boiler configuration front mounted display display may be in alternate location on the burner end access panel Boiler components Boiler manual gas valve Boiler manual gas valve Switch...

Page 6: ...6 SlimFit Series 2 commercial condensing gas fired water boiler User s Information Manual Part number 550 100 181 0517 The Control display Figure 5 SlimFit boiler s control display...

Page 7: ...lect MANUAL RESET to reset boiler as shown below Date and time 1 Set month date year hour and minutes 2 Keeping the date and time current makes sure the control can record problems ac curately BOILER...

Page 8: ...reset boiler as shown below To reset Press the DOWN or RIGHT arrow The display will go to the STATUS screen SETTINGS will be highlighted Press the DOWN arrow to move down to MANUAL RESET Press ENTER...

Page 9: ...building Pleasereadtheinformationlistedbelow Ifcontaminatingchemicalswillbepresentnearthelocationoftheboiler combustionairinlet haveyourinstallerpipetheboilercombustionairandventtoanotherlocation pert...

Page 10: ...ter cutoff Check time and date on the control display EVERY 6 MONTHS Check boiler piping gas and water Operate relief valve END OF SEASON Shut boiler down unless boiler used for domestic water Follow...

Page 11: ...cted and started annually at the beginning of the heating season by a qualified service technician In addition the maintenance and care of the boiler listed on Figure 10 page 10 and explainedinthisman...

Page 12: ...mmediately or the boiler combustion air and vent termination must be relocated to another area Check the pressure temperature gauge 1 Make sure the pressure reading on the boiler pressure tempera ture...

Page 13: ...condensate trap if problem persists regularly Under some circumstances an SlimFit vent system may not produce enough condensate to keep the condensate trap full of liquid If the trap is not full smal...

Page 14: ...ThegreenSTATUSlightshouldchangetored indicat ing a low water condition 5 The SlimFit boiler s control will shut down the boiler on manual reset 6 The control display will flash red as shown in Figure...

Page 15: ...scharge pipe to ensure that the valve does not weep after the line has had time to drain If the valve weeps lift the seat again to attempt to clean the valve seat If the valve continues to weep afterw...

Page 16: ...SlimFit Series 2 commercial condensing gas fired water boiler User s Information Manual...

Reviews: