![Weil-McLain GOLD CGa Manual Download Page 57](http://html1.mh-extra.com/html/weil-mclain/gold-cga/gold-cga_manual_952708057.webp)
Part Number
550-101-009/0107
57
GOLD CGa Gas-Fired Water Boiler — Boiler Manual
• Turn off power to the boiler at service switch or breaker.
• Wait at least 45 seconds.
• Turn on power to boiler.
• Restart boiler, following
Operating instructions
in this
manual (Section 9b) or on boiler label.
• Look through the pilot inspection port to see if the pilot is
burning.
Is pilot burning?
Electrical shock hazard — Wherever you see
TURN OFF POWER
, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
• Leave main manual gas valve closed.
• Turn off power to boiler at service switch or breaker.
• Wait at least 45 seconds.
• Turn on power to boiler.
• Restart boiler, following
Operating instructions
in this
manual (Section 9b) or on boiler label.
Do
FLAME
and
POWER
lights still flash?
• Boiler should now
operate normally.
• Original flashing
FLAME light
caused by gas
valve not
operating properly.
• See normal
sequence of
operation,
Figure 24
,
page 37.
• Replace gas valve.
• Retest boiler.
Are
FLAME
and
POWER
lights flashing?
No
Yes
No
Yes
Are manual main shutoff valve and gas valve open?
• Replace control module.
• Retest.
— Usually indicates flame sensed when it shouldn't be there —
Yes
No
•
TURN OFF POWER
to boiler at service switch
or breaker.
• Open main manual gas
valve.
• Turn on power to boiler
at service switch or
breaker.
• Restart boiler per
operating instructions.
• Perform start-up
procedures in boiler
manual to verify proper
operation.
• Allow boiler to continue cycling.
Are
FLAME
and
POWER
lights flashing?
No
Yes
No
Yes
• Replace control
module.
• Retest.
• Replace control
module.
• Retest.
• Boiler may now be
operating
normally.
• Perform start-up
procedures in
boiler manual to
verify proper
operation.
CHART 5
—
Spark-ignited pilot
—
FLAME & POWER
lights flashing
Troubleshooting — spark-pilot boilers
(continued)
11c