Weil-McLain EG-30 THRU -75 Control Supplement Download Page 20

0

Part Number 550-110-032/0607

EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4

Figure 11

1.  Checking thermocouple or thermopile open system (Figure 10):

a.  Use an electronic multimeter, with leads fitted with alligator clips. Set meter 

scale to DC Millivolts.

b.  Unscrew thermocouple or thermopile fitting from gas valve.
c.  Attach one meter lead to the end of the thermocouple or thermopile gas 

valve fitting.

d.  Attach other meter lead to thermocouple or thermopile lead (copper sur-

face).

e.  Follow Lighting Instruction label on boiler (also found in Control Supple-

ment or User’s Information Manual) to light the pilot burner only, and hold 
the pilot flame manually. (DO NOT light main burner.)

f.  Check the reading on the multimeter. The reading should be around 8 

millivolts for a thermocouple, or 00 millivolts for a thermopile.

g.  If  multimeter  reading  is  significantly  less  than  above  and  pilot  flame  is 

appropriate, replace the thermocouple or thermopile.

.  Checking thermopile and high limit control circuit closed system (Fig-

ure 11):

a.  Use an electronic multimeter, with leads fitted with alligator clips. Set meter 

scale to DC Millivolts.

b.  Loosen the insulated terminal on the TOP thermopile lead wire enough to 

allow clipping a multimeter alligator clip to the spade terminal.

c.  Attach the other multimeter lead to the thermopile lead (copper surface). 

Light the pilot burner per step 1 e, above.

d.  Check the reading on the multimeter. The reading should be around 00 

millivolts.

e.  If reading is significantly less than 00 millivolts, check tightness of lead 

wire  assembly  in  gas  valve.  If  the  connections  are  secure  and  you  have 
checked the thermopile per step 1 above, replace the thermopile lead wire 
assembly.

f.  If reading on TOP thermopile lead wire is around 00 millivolts, move the 

multimeter alligator clip to the BOTTOM thermopile lead wire terminal 
and check multimeter reading.

g.  If multimeter does not read around 00 millivolts, check wiring connections 

and wire integrity to the high limit control.

h.  Check voltage at each limit terminal to make sure limit is closed. Correct 

pressure or temperature condition causing any limit to be open. Replace 
limit if necessary.

Pilot does not stay lit — 

Troubleshooting thermocouple or thermopile 

and high limit control circuit

Figure 10

Troubleshooting 

continued

Summary of Contents for EG-30 THRU -75

Page 1: ...ntrol supplement Standing pilot This supplement must only be used by a qualified heating installer service technician Before installing read all instructions including this supplement the boiler manua...

Page 2: ...Note to the installer Controls must only be installed by a Weil McLain distributor or other qualified installer service technician in accordance with this Supplement and all applicable codes and requ...

Page 3: ...out tankless heaters 4 5 Control installation EG 30 thru 65 water boilers with tankless heaters 6 7 Control installation EG 30 thru 75 and PEG 30 thru 65 steam boilers with probe 8 9 Control installat...

Page 4: ...Part Number 550 110 032 0607 EG 30 thru 75 Series 4 and PEG 30 thru 65 Series 4...

Page 5: ...d wire controls per wiring diagram page 4 and Figure 2 a Attach junction box inside left jacket panel with 8 32 x machine screws and green ground nuts provided b Install transformer with plug in relay...

Page 6: ...Part Number 550 110 032 0607 EG 30 thru 75 Series 4 and PEG 30 thru 65 Series 4...

Page 7: ...Figure 3 a Install combination limit control and relay in tap ping See Boiler Manual control tapping table Op erating and limit circuit wiring must be 14 gauge or heavier 2 Bring supply wiring to boil...

Page 8: ...Part Number 550 110 032 0607 EG 30 thru 75 Series 4 and PEG 30 thru 65 Series 4...

Page 9: ...ith probe type low water cutoff EG 30 thru 65 and PEG 30 thru 65 steam boilers with probe type low water cutoff Control installation continued 1 Mount and wire controls per wiring diagram page 8 and F...

Page 10: ...10 Part Number 550 110 032 0607 EG 30 thru 75 Series 4 and PEG 30 thru 65 Series 4...

Page 11: ...boilers with float type low water cutoff EG 30 thru 65 steam boilers with float type low water cutoff Control installation continued 1 Mount and wire controls per wiring diagram page 10 and Figure 6...

Page 12: ...0 thru PEG 65 steam natural gas The following boiler models may have damper installed EG 75 natural or propane gas Once damper is installed boiler will not operate without a damper installed Only damp...

Page 13: ...rial Provide a minimum of 46 between jacket top and combustible ceiling See EG PEG EGH Boiler manual for complete clearance requirements Installation Do not modify draft hood or damper or make another...

Page 14: ...ructions 2 Raise room thermostat to call for heat Damper actuator will slowly open damper 3 When damper is fully open main gas valve will open and main burners will ignite Damper must be fully open be...

Page 15: ...15 Part Number 550 110 032 0607 Standing Pilot Boilers Control Supplement Lighting instructions Robertshaw 7200...

Page 16: ...16 Part Number 550 110 032 0607 EG 30 thru 75 Series 4 and PEG 30 thru 65 Series 4 Lighting instructions Honeywell VR8200 VR8300 Natural gas boilers only...

Page 17: ...17 Part Number 550 110 032 0607 Standing Pilot Boilers Control Supplement Lighting instructions Honeywell VR8200 VR8300 Propane boilers only...

Page 18: ...18 Part Number 550 110 032 0607 EG 30 thru 75 Series 4 and PEG 30 thru 65 Series 4 Lighting instructions Robertshaw 7000ERHC...

Page 19: ...severe personal injury death or substantial property damage 2 Refer to vent damper manufacturer s instructions for procedure to fix vent damper in open position 3 Turn on power to boiler 4 Using wrenc...

Page 20: ...timeter with leads fitted with alligator clips Set meter scale to DC Millivolts b Loosen the insulated terminal on the TOP thermopile lead wire enough to allow clipping a multimeter alligator clip to...

Page 21: ...21 Part Number 550 110 032 0607 Standing Pilot Boilers Control Supplement Troubleshooting continued...

Page 22: ...22 Part Number 550 110 032 0607 EG 30 thru 75 Series 4 and PEG 30 thru 65 Series 4 Troubleshooting continued...

Page 23: ...23 Part Number 550 110 032 0607 Standing Pilot Boilers Control Supplement Troubleshooting continued...

Page 24: ...BE 1C 510 512 337 510 312 255 Damper harness Weil McLain 591 391 795 Boiler wiring harness EG 30 thru 75 water EG 35 thru 65 water with tankless EG 30 thru 75 steam float LWCO EG 30 thru 75 PEG 30 thr...

Reviews: