Short Form Data

Programmable
Multi -Functional Trans-
ducer for AC Currents, 
AC Voltages and Powers

MMU 3.0

=

RS232

RS485

with 

m

P

Inputs

input quantities

AC current and AC voltage
in single phase or 3 phase system

voltages

L1, L2, L3 (3 terminals), N (1 terminal)

600V (inter - connected) or optional N/120V (also for N/100V or N/110V)
currents

I1, I2, I3 (6 terminals)
N/5 A or optional N/1.2 A (also for N/1 A)

Measuring Quantity

Total

L1

L2

L3

voltage (U)

U

U

1

U

2

U

3

current (I)

I

I

1

I

2

I

3

active power (P)

P

P

1

P

2

P

3

reactive power (Q)

Q

Q

1

Q

2

Q

3

apparent power (S)

S

S

1

S

2

S

3

active factor (PF)

PF

PF

1

PF

2

PF

3

reactive factor (QF)

QF

QF

1

QF

2

QF

3

phase angle (PH)

PH

PH

1

PH

2

PH

3

frequency (f)

F

Depending on power system, not all these values van be measured.

10 V measuring input

INP

(±10 V)

Other Ratings

analog output 1

voltage & current synchronous 
(2 terminals each) 

refer to 

General Data

interfaces

RS 232 (SUB–D jack), RS 485 (2 terminals)

digital output

contactāĆāfree via opto coupler

1, 2, or 3 additional analog outputs (galvanically isolated) and 
up to 8 additional digital outputs (galvanically isolated) are optional

accuracy

class 0.5

 (

±

0.5% of end value)

auxiliary voltage

wide range supply 

refer to 

General Data

dimensions

basic version: 3 modules in single - phase 
resp. 4 modules in three - phase systems, 
optional outputs: additional 1 to 3 modules

each module WxHxL

22.5 mm x 80 mm x 115 mm

weight

approx. 0.6 kg (basic version)

for detailed information

refer to Data Sheet No. 055.##

prices

refer to Price Sheet No. 055.##

Short Form Data

Transducers for
Active Power and
Reactive Power

DUW 2.1
DUB 2.1
VUW 2.1
VUB 2.1

=

P/Q

Inputs

input rating

sinusoidal AC current and
sinusoidal AC voltage

input quantity P

E

active or reactive power

type

active / reactive power

3 - phase 3 - wire system unbalanced load

DUW 2.1

DUB 2.1

3 - phase 4 - wire system unbalanced load

VUW 2.1

VUB 2.1

measuring range

0 ... P

N

 or –P

N

 ... 0 ... P

N

P

N

= (0.3 ... 1.5) . P

S

P

S

 =  3 . U . I

rated input voltage U

EN

65 V, 100 V, 110 V, 240 V, 400 V, 415 V, 440 V, 
500 V, 600 V or deviating from standard inputs 
ranging from 0 ... (60 V ... U

EN

 ... 600 V)

rated input current I

EN

N/1 A, N/5 A or deviating from standard inputs 

ranging from

 0 ... (0,5 A ... I

EN

 ... 5 A)

modulation range

1.2 U

EN

 and 1.2 I

EN

overload limits

1.2 U

EN

,

 

1.2 I

EN 

continuously

2    U

EN

,

 

10  I

EN

 1 s max.

frequency range

50 Hz (48 ... 52 Hz) or
16

2

/

3

 Hz, 60 Hz, 100 Hz, others on request

power consumption

<1 mA each voltage circuit

0.1 VA each current circuit for I

EN

 = 1 A

1.6 VA each current circuit for I

EN

 = 5 A

Other Ratings

outputs

refer to 

General Data

accuracy

class 0.5

 (

±

0.5% of end value)

auxiliary voltage

refer to 

General Data

dimensions

 WxHxL

45 mm x 80 mm x 115 mm

weight

DUW/DUB 2.1

VUW/VUB 2.1

approx. 0.29 kg

approx. 0.31 kg

for detailed information

refer to Data Sheet No. 051.##

prices

refer to Price Sheet No. 051.##

Summary of Contents for A1U 2.2

Page 1: ...ional Transducer MMU 3 0 for Frequency FU 2 2 for Phase Angle cos CU 2 2 for DC Current or DC Voltage AUD VUD 2 2 for RMS Current or RMS Voltage AUE VUE 2 2 for Temperature PTU 2 0 Isolation Transduce...

Page 2: ...UA load independent DC voltage 0 10 V or optionally2 10 V live zero 10 0 10 V bipolar output only with wide range supply load RA 4 kW load error 0 1 based on 50 load change residual ripple 1 rms resp...

Page 3: ...nd Reactive Power EW 2 2 EB 2 2 DGW 2 2 VGW 2 2 DUW 2 2 VUW 2 2 DGB 2 2 VGB 2 2 DUB 2 2 VUB 2 2 P Q with mP Inputs input quantity sinusoidal AC current voltage measuring unit PE active or reactive pow...

Page 4: ...os CU 2 2 with mP Inputs input quantity sinusoidal AC current voltage measuring unit phase angle power factor in E single phase AC system or D 3 phase 3 wire balanced load system measuring ranges 37 0...

Page 5: ...tional outputs additional 1 to 3 modules each module WxHxL 22 5 mm x 80 mm x 115 mm weight approx 0 6 kg basic version for detailed information refer to Data Sheet No 055 prices refer to Price Sheet N...

Page 6: ...d value class 0 2 0 2 of end value only for DC models on request auxiliary voltage refer to General Data dimensions WxHxL 22 5 mm x 80 mm x 115 mm weight approx 0 12 kg for detailed information refer...

Page 7: ...RS232 RS485 Converter AP RS232 485 RS232 RS485 Function The converter is directly plugged to a 9 contact serial interface of a PC It converts the RS232 signals of the PC into standardized RS485 signal...

Page 8: ...dependent DC current rated current IAN 4 20 mA load range RA 0 500 W based on 20 mA load error 0 1 based on 50 load change residual ripple 1 rms of IAN with load RAN idling voltage 16 V response time...

Reviews: