- 5 -
DIN-Rail Mounting
The aluminum DIN-Rail attachment plate should already be fixed to the back
panel of the IE-SW-PL10M when you take it out of the box. If you need to
reattach the DIN-Rail attachment plate to the IE-SW-PL10M, make sure the
stiff metal spring is situated towards the top, as shown by the following
figures.
STEP 1
—
Insert the top of the
DIN-Rail into the slot just below the
stiff metal spring.
STEP 2
—
The DIN-Rail attachment
unit will snap into place as shown in
the following illustration.
To remove the IE-SW-PL10M switch from the DIN-Rail, simply reverse Steps
1 and 2 above.
ATEX Information
1.
Certificate number DEMKO 11 ATEX 150190X
2.
Ambient range (-40°C ≤ Tamb ≤ 75°C)
3.
Certification string (Ex nA nC IIC T4 Gc)
4.
Standards covered (EN 60079-0:2012+A11:2013,
EN 60079-15:2010)
5.
The conditions of safe usage:
These products must be mounted in an IP54 enclosure.
Install in an area of pollution degree 2 or less.
Use a conductor wire of size 0.2 mm² or greater.
PROVISIONS SHALL BE MADE, EITHER IN EXTERNAL TO
THE APPARATUS, TO PREVENT THE RATED VOLTAGE BEING
EXCEEDED BY THE TRANSIENTS DISTURBANCES OF MORE
THAN 40 %
Wiring Requirements
WARNING
Do not disconnect modules or wires unless power has been
switched off or the area is known to be non-hazardous. The
devices may only be connected to the supply voltage shown on
the type plate. The devices are designed for operation with a
Safety Extra-Low Voltage. Thus, they may only be connected to
the supply voltage connections and to the signal contact with the
Safety Extra-Low Voltages (SELV) in compliance with IEC950/
EN60950/ VDE0805.