OBJECT DICTIONARY
Table 7.2:
Object list – Communication Profile
Index
Object
Name
Type
Access
1000h
VAR
device type
UNSIGNED32
ro
1001h
VAR
error register
UNSIGNED8
ro
1005h
VAR
COB-ID SYNC
UNSIGNED32
rw
100Ch
VAR
quard time
UNSIGNED16
rw
100Dh
VAR
life time factor
UNSIGNED8
rw
1016h
ARRAY
consume heartbeat time
UNSIGNED32
rw
1017h
VAR
producer heartbeat time
UNSIGNED16
rw
1018h
RECORD
Identity Object
Identity
ro
Server SDO Parameter
1200h
RECORD
1st Server SDO parameter
SDO Parameter
ro
Receive PDO Communication Parameter
1400h
RECORD
1st receive PDO Parameter
PDO CommPar
rw
1401h
RECORD
2nd receive PDO Parameter
PDO CommPar
rw
1402h
RECORD
3rd receive PDO Parameter
PDO CommPar
rw
1403h
RECORD
4th receive PDO Parameter
PDO CommPar
rw
Receive PDO Mapping Parameter
1600h
RECORD
1st receive PDO mapping
PDO Mapping
rw
1601h
RECORD
2nd receive PDO mapping
PDO Mapping
rw
1602h
RECORD
3rd receive PDO mapping
PDO Mapping
rw
1603h
RECORD
4th receive PDO mapping
PDO Mapping
rw
Transmit PDO Communication Parameter
1800h
RECORD
1st transmit PDO Parameter
PDO CommPar
rw
1801h
RECORD
2nd transmit PDO Parameter
PDO CommPar
rw
1802h
RECORD
3rd transmit PDO Parameter
PDO CommPar
rw
1803h
RECORD
4th transmit PDO Parameter
PDO CommPar
rw
Transmit PDO Mapping Parameter
1A00h
RECORD
1st transmit PDO mapping
PDO Mapping
rw
1A01h
RECORD
2nd transmit PDO mapping
PDO Mapping
rw
1A02h
RECORD
3rd transmit PDO mapping
PDO Mapping
rw
1A03h
RECORD
4th transmit PDO mapping
PDO Mapping
rw
These objects can only be read and written via the CANopen network, it is not available via the keypad (HMI) or other
network interface. The network master, in general, is the equipment responsible for setting up the equipment before
starting the operation. The EDS configuration file brings the list of all supported communication objects.
Refer to item 8 for more details on the available objects in this range of the objects dictionary.
7.4 MANUFACTURER SPECIFIC OBJECTS
For indexes from 2000h to 5FFFh, each manufacture is free to define which objects will be present, and also the
type and function of each one. In the case of the SSW900, the whole list of parameters was made available in this
object range. It is possible to operate the SSW900 by means of these parameters, carrying out any function that the
inverter can execute. The parameters were made available starting from the index 2000h, and by adding their Net Id
to this index their position in the dictionary is obtained. To identify how the parameters are distributed in the object
dictionary, refer to the Appendix A.
In order to be able to program the SSW900 operation correctly via the CANopen network, it is necessary to know its
operation through the parameters.
Refer to the SSW900 soft-starter programming manual for a complete list of the parameters and their detailed
description.