SSW06 Installation Guide
Page 9
ENGL
ISH
USE OF THE HMI
Programming keys:
Toggles the LED display between the parameter number
and its value (position / content).
Increases the number of the parameter or the value of the
parameter.
Decreases the number of the parameter or the value of the
parameter.
Command selecting keys:
Toggles between LOCAL or REMOTE modes of operation.
Parameter: P220 = 2 or 3.
NOTE!
In the factory default settings the commands for keys of
the HMI are enabling when the Local will be selected.
Command keys:
Enable the motor (start).
After starting, at each touch it commutates the fast access
indication on the display.
Disable the motor (stop).
It resets the SSW06 after a fault trip.
Reverses the motor direction of rotation. By contactor or
JOG Only.
Parameter: P231.
When the Jog key is pressed realize the Jog function (if the
motor is not enabled, the SSW06 is with General Enable
active and Jog is not enabled).
Parameters: P51X.
NOTE!
These functions can be executed via: digitals inputs,
communication serial, fieldbus or SoftPLC.
Parameters: P220, P229 and P230.
Parameter viewing and programming:
LED
Initial screen at power-up.
Press the key
.
Rdy
LCD
Soft-Starter
Ready
LED
Use the keys
and
.
Select the desired parameter.
P002
LCD
Motor Current
P002= 0.0%
LED
For example, change P101.
Press the key
.
P101
LCD
Init. Volt. Start
P101= 30%
LED
Value to be change.
30
LCD
Init. Volt. Start
P101= 30%
NOTE!
To allow the reprogramming of any parameter value it is
necessary to change parameter P000 to the password
value. The factory default password value is 5. Otherwise
you can only read the parameter values and not
reprogram them.
LED
Use the keys
and
change
the value of parameter.
35
LCD
Init. Volt. Start
P101= 35%
LED
Press the key
and the value is
saved.
P101
LCD
Init. Volt. Start
P101= 35%
NOTE!
For parameters that can be changed with the motor
running, the SSW06 will use the new value immediately
after it has been set. For the parameters that can be
changed only with the motor stopped,
the SSW06 will use this new set value only after the key
is pressed with the motor disable.
NOTE!
If the last value programmed in the parameter is not
functionally compatible with other parameter values
already programmed, an E24 –Programming Error – will
be displayed.