INTERFACE DESCRIPTION
2.5 TERMINATING RESISTOR
The product has a switch (S4) that can be activated to enable the termination resistor according to figure 2.1. The
configurations of the switch to enable the termination resistor are shown in table 2.3.
Table 2.3:
Configurations of the switch (S4) that enables the termination resistor
Switch Setting
Option
SW.1 = OFF and SW.2 = OFF
CAN termination off
SW.1 = ON and SW.2 = ON
CAN termination on
SW.1 = OFF and SW.2 = ON
Combination not allowed
SW.1 = ON and SW.2 = OFF
2.6 INDICATION LED
The SCW100 starter manager has a bicolor LED (green and red), as shown in figure 2.1, the tables below show the
behavior of these LEDs depending on the status of the starter manager:
Table 2.4:
LED NET - GREEN
Indication
State
Description
Off
-
Powered off.
Green, one flash
Stopped
Device is in the ”Stopped” state. PDOs and SDOs are not
available at this state.
Green, alternating each 200ms
Pre-operational
Device is in the ”Pre-operational” state. PDOs are not
available for communication.
Green, solid
Operational
Device is in the ”Operational” state.
Table 2.5:
LED NET - RED
Indication
State
Description
Off
No error
Device is operating normally.
Red, one flash
Warning or Passive
Indicates the CAN interface is in Warning or Error Passive
state. It may occur, for instance, it is the only device
connected to network.
Red, two flashes
Node Guarding or Heartbeat
error
An comminication error has been detected using CANopen
error control mechanism - guarding or heartbeat.
Red, solid
BUS OFF error
CAN interface is in the bus-off state. It indicates a critical
communication error condition, normally associated with
installation problems or incorrect baud rate configuration.
It is necessary to power cycle the device to restore
communication.
Red, alternating each 50ms
CANopen not initialized
CANopen communication could not be properly initialized.
Verify if it is configured to a valid address (01h – 7Fh).
SCW100 | 10