5
DETAILED PARAMETER DESCRIPTION
P0066 - MVC3 board software version
Acesso:
Menu
→
Status
→
Inverter
→
Software version
Description:
It indicates the software version contained in the microcontroller memory of the MVC3 control board.
P0067 - Error Register
Adjustable range:
1 to 100
Factory setting:
1
Acesso:
Menu
→
Diagnostics
→
Alarms n’ faults
Description:
It keeps the record of the last 100 errors (alarms/faults) occurred in the inverter.
P0068 - Present Error
Acesso:
Menu
→
Diagnostics
→
Alarms n’ faults
Description:
It indicates the code of the current fault on the inverter.
P0070 - Status of the MVC3 board digital inputs DI1, DI2, ..., DI16
Acesso:
Menu
→
Status
→
I/O
→
Digital
Description:
It indicates, on the Graphic HMI, the status of 16 digital inputs of the MVC3 control board (DI1 to DI16), by
means of the letters A (Active) and I (Inactive), in the following order:
DI1, DI2, ... , DI15, DI16
Table 5.5:
Status of the MVC3 board digital inputs DI1, DI2, ..., DI16
Description
Bit
DI16 - State of mechanically locked doors
Bit 0
DI15 - Not used
Bit 1
DI14 - Not used
Bit 2
DI13 - General enable
Bit 3
DI12 - Inverter main transformer fault
Bit 4
DI11 - Inverter main transformer alarm
Bit 5
DI10 - Cooling system supply fault
Bit 6
DI9 - Not used
Bit 7
DI8 - Not used
Bit 8
DI7 - Pre-charge supply fault
Bit 9
DI6 - See P1739 (RL8 Function MVC3)
Bit 10
DI5 - Enabling of the input protection
Bit 11
DI4 - Circuit breaker OFF state
Bit 12
DI3 - Circuit breaker ON state
Bit 13
DI2 - Circuit breaker Ready
Bit 14
DI1 - Power ON (Starts pre-charge)
Bit 15
MVW3000 | 5-9