Logical Command and Speed Reference
7-12 | CFW501
7
P0682 – Serial / USB Control
Adjustable
Range:
0000h to FFFFh
Factory
Setting:
Properties:
ro
Access groups
via HMI:
NET
Description:
The inverter control word for a certain source is accessible for reading and writing, but read only access is
permitted for the other sources. The inverter has a common word for interface, which is defined by the function
of its bits separately as per
Table 7.5: Control word (P0682) on page 7-12
.
Table 7.5:
Control word (P0682)
BIT
Function
Description
0
Enable Ramp
0:
Stops the motor by deceleration ramp.
1:
Turn the motor according to the acceleration ramp until reaching the speed reference value.
1
Enable General
0:
Disable the inverter completely, interrupting the power supply to the motor.
1:
Enable completely the inverter, allowing the operation of the motor.
2
Run Clockwise
0:
Run the motor in the opposite direction of the reference signal (counter clockwise).
1:
Run the motor in direction of the reference signal (clockwise).
3
JOG Enable
0:
Disable JOG function.
1:
Enable JOG function.
4
Remote
0:
Inverter goes into local mode.
1:
Inverter goes into remote mode.
5
2
nd
Ramp
0:
Acceleration and deceleration ramp by P0100 and P0101.
1:
Acceleration and deceleration ramp by P0102 and P0103.
6
Quick Stop
0:
It does not execute the fast stop command.
1:
It executes the fast stop command.
7
Fault Reset
0:
No function.
1:
If in fault state, reset the fault.
8 to 12
Reserved
13
Internal PID
Controller
0:
Automatic.
1:
Manual.
14
External PID
Controller
0:
Automatic.
1:
Manual.
15
Reserved
Summary of Contents for CFW501 V1.8X
Page 2: ......
Page 8: ...Summary...
Page 34: ...General Information 2 4 CFW501 2...
Page 38: ...About the CFW501 3 4 CFW501 3...
Page 42: ...HMI and Basic Programming 4 4 CFW501 4...
Page 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Page 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Page 76: ...Available Motor Control Types 8 4 CFW501 8...
Page 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Page 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Page 148: ...Faults and Alarms 14 12 CFW501 14...