Basic Instructions for Programming and Settings
CFW501 | 5-11
5
5.5 BACKUP PARAMETERS
The CFW501 BACKUP functions allow saving the inverter current parameter contents in a specific memory
(EEPROM), or vice-versa overwrite the current parameters with the content of the specified memory.
P0204 – Load / Save Parameters
Adjustable
Range:
0...2 = Not Used
3 = Reset P0043
4 = Reset P0044
5 = Load WEG 60 Hz
6 = Load WEG 50 Hz
7 = Load user 1
8 = Load user 2
9 = Save user 1
10 = Save user 2
11 = Load Standard SoftPLC
12...15 = Reserved
Factory
Setting:
0
Properties:
cfg
Description:
It allows saving the inverter present parameters in a non-volatile memory (EEPROM) of the control module or
the opposite, loading the parameters with the content of this area.
Table 5.3: Option of parameter P0204 on
describes the actions performed
by each option.
Table 5.3:
Option of parameter P0204
P0204
Action
0...2
Not Used:
No action.
3
Reset P0043:
resets the enabled hours counter.
4
Reset P0044:
resets the kWh counter.
5
Load WEG 60 Hz:
It loads the default parameters on the inverter with the factory default for 60 Hz.
6
Load WEG 50 Hz:
It loads the default parameters on the inverter with the factory default for 50 Hz.
7
Load user 1:
It transfers the content of the memory of parameters 1 to the inverter current parameters.
8
Load user 2:
It transfers the content of the memory of parameters 2 to the inverter current parameters.
9
Saver user 1:
It transfers the current content of the parameters to the memory of parameters 1.
10
Saver user 2:
It transfers the current content of the parameters to the memory of parameters 2.
11
Load Standard SoftPLC:
It loads the default values of the parameters SoftPLC applicative parameters.
12...15
Reserved:
No Action
In order to load the parameters of user 1 and/or user 2 to the CFW501 operating area (P0204 = 7 or 8), it is
necessary that those areas be previously saved.
The operation of loading one of those memories (P0204 = 7 or 8) can also be done via digital inputs (DIx). For
further details referring to this programming, refer to
section 12.5 DIGITAL INPUTS on page 12-15
NOTE!
When P0204 = 5 or 6, parameters P0296 (Rated voltage), P0297 (Switching frequency) P0312 (Serial
Protocol) and P0308 (Serial address) are not changed to the factory default.
Summary of Contents for CFW501 V1.8X
Page 2: ......
Page 8: ...Summary...
Page 34: ...General Information 2 4 CFW501 2...
Page 38: ...About the CFW501 3 4 CFW501 3...
Page 42: ...HMI and Basic Programming 4 4 CFW501 4...
Page 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Page 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Page 76: ...Available Motor Control Types 8 4 CFW501 8...
Page 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Page 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Page 148: ...Faults and Alarms 14 12 CFW501 14...