Digital and Analog Inputs and Outputs
CFW300 | 12-3
12
Description:
These parameters define the analog inputs functions.
When the 0 option is selected (Reference Frequency), the analog inputs can provide the reference for the motor,
subject to the specified limits (P133 and P134) and to the action of the ramps (P100 to P103). However, in order
to do so, it is also necessary to configure parameters P221 and/or P222, by selecting the use of the desired
analog input. For further detail, refer to the description of those parameters in
AND FREQUENCY REFERENCE on page 7-1
Option 4 (PTC) configures the input to monitor the motor temperature. For further details on this function, refer
Section 14.4 OVERCURRENT PROTECTION (F070) on page 14-4
.
Option 7 (PLC Use) configures the input to be used by the programming done in the memory area reserved for
the SoftPLC function. For further details, refer to the SoftPLC user’s manual.
Options 16 and 17 configure the input for the use of the PID Controller application (P903 = 1). For further details,
see
Chapter 18 APPLICATIONS on page 18-1
.
P232 - AI1 Input Gain
P237 - AI2 Input Gain
Adjustable
Range:
0.000 to 9.999
Factory
Setting:
1.000
P234 - AI1 Input Offset
P239 - AI2 Input Offset
Adjustable
Range:
-100.0 to 100.0 %
Factory
Setting:
0.0 %
P235 - AI1 Input Filter
P240 - AI2 Input Filter
Adjustable
Range:
0.00 to 16.00 s
Factory
Setting:
0.00 s
Properties:
Summary of Contents for CFW300 V1.3X
Page 2: ......
Page 8: ...Contents...
Page 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Page 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Page 72: ...V f Scalar Control 9 10 CFW300 9...
Page 80: ...VVW Vector Control 10 8 CFW300 10...
Page 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Page 132: ...Reading Parameters 15 6 CFW300 15...