VVW Vector Control
CFW300 | 10-3
10
10.1 VVW VECTOR CONTROL PARAMETERIZATION
The V VW control mode is selected by parameter P202, control mode selection, as described in
AVAILABLE MOTOR CONTROL TYPES on page 8-1
.
Opposite to the V/f scalar control, the V VW control requires a series of data from the motor nameplate and a
self-tuning for its proper operation. Besides, it is recommended that the driven motor match the inverter, that is,
the motor and inverter power be as close as possible.
Below are described the parameters to configure the V VW vector control setting. This data is easily obtained on
WEG standard motor nameplates, however in older motors or motors made by other manufacturers, the data
may not be readily available. In those cases, it is recommended first contact the motor manufacturer, measure or
calculate the desired parameter. As a last resort, the user always can make a relationship with
and use the equivalent or approximate WEG standard motor parameter.
NOTE!
The correct setting of the parameters directly contributes to the V VW control performance.
Table 10.1:
Characteristics of IV pole WEG standard motors
Power [P404]
Frame
size
Voltage
[P400]
(V)
Current
[P401]
(A)
Frequency
[P403]
(Hz)
Speed
[P402]
(rpm)
Efficiency
[P399]
(%)
Power
Factor
Stator
Resistance
[P409]
(Ω)
(HP)
(kW)
0.16
0.12
63
220
0.85
60
1720
56.0
0.66
21.77
0.25
0.18
63
1.12
1720
64.0
0.66
14.87
0.33
0.25
63
1.42
1720
67.0
0.69
10.63
0.50
0.37
71
2.07
1720
68.0
0.69
7.37
0.75
0.55
71
2.90
1720
71.0
0.70
3.97
1.00
0.75
80
3.08
1730
78.0
0.82
4.13
1.50
1.10
80
4.78
1700
72.7
0.83
2.78
2.00
1.50
90S
6.47
1720
80.0
0.76
1.55
3.00
2.20
90L
8.57
1710
79.3
0.85
0.99
4.00
3.00
100L
11.6
1730
82.7
0.82
0.65
5.00
3.70
100L
13.8
1730
84.6
0.83
0.49
0.16
0.12
63
230
0.73
50
1375
57.0
0.72
30.62
0.25
0.18
63
1.05
1360
58.0
0.74
20.31
0.33
0.25
71
1.4
1310
59.0
0.76
14.32
0.50
0.37
71
1.97
1320
62.0
0.76
7.27
0.75
0.55
80
2.48
1410
68.0
0.82
5.78
1.00
0.75
80
3.23
1395
72.0
0.81
4.28
1.50
1.10
90S
4.54
1420
77.0
0.79
2.58
2.00
1.50
90L
5.81
1410
79.0
0.82
1.69
3.00
2.20
100L
8.26
1410
81.5
0.82
0.98
4.00
3.00
100L
11.3
1400
82.6
0.81
0.58
5.00
3.70
112M
14.2
1440
85.0
0.83
0.43
P178 - Rated Flux
Adjustable
Range:
50.0 to 150.0 %
Factory
Setting:
100.0 %
Properties:
V VW
Description:
It defines the desired flux in the motor air gap in percentage (%) of the rated flux. In general, it is not necessary
to modify the value of P178 of the standard value of 100 %. However, some specific situations may use values
slightly above to increase the torque, or below to reduce the energy consumption.
Summary of Contents for CFW300 V1.3X
Page 2: ......
Page 8: ...Contents...
Page 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Page 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Page 72: ...V f Scalar Control 9 10 CFW300 9...
Page 80: ...VVW Vector Control 10 8 CFW300 10...
Page 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Page 132: ...Reading Parameters 15 6 CFW300 15...