Digital and Analog Inputs and Outputs
12-14 | CFW300
12
P271 - Digital Input Signal
Adjustable
Range:
0 = All DIx NPN
1 = (DI1...DI4) - PNP
2 = (DI5...DI8) - PNP
3 = (DI1...DI8) - PNP
Factory
Setting:
0
Properties:
cfg
Description:
It configures the default for the digital input signal, that is, NPN and the digital input is activated with 0 V, PNP
and the digital input is activated with +24 V.
a) RUN/STOP
It enables or disables the motor rotation through the acceleration and deceleration ramp.
Acceleration
ramp
Deceleration
ramp
Time
Time
Active
Inactive
DIx
Output
frequency
Figure 12.5:
Example of the Run/Stop function
b) GENERAL ENABLE
It enables the motor rotation through the acceleration ramp and disables it by cutting off the pulses immediately;
the motor stops by inertia.
Acceleration ramp
Motor runs free
Time
Time
Active
Inactive
DIx
Output
frequency
Figure 12.6:
Example of the General Enable function
c) QUICK STOP
When inactive, it disables the inverter by the emergency deceleration (P107).
Acceleration
ramp
P107 -
Deceleration
ramp
Time
Time
Active
Inactive
DIx
Output
frequency
Figure 12.7:
Example of the Quick Stop function
Summary of Contents for CFW300 V1.3X
Page 2: ......
Page 8: ...Contents...
Page 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Page 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Page 72: ...V f Scalar Control 9 10 CFW300 9...
Page 80: ...VVW Vector Control 10 8 CFW300 10...
Page 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Page 132: ...Reading Parameters 15 6 CFW300 15...