Digital and Analog Inputs and Outputs
CFW300 | 12-9
12
12.4 FREQUENCY INPUT
A frequency input consists of a fast digital input able to convert the frequency of the pulses in the input into a
proportional signal with 15-bit resolution. After the conversion, this signal is used as an analog signal for frequency
reference, process variable, for example.
According to the block diagram of
, the signal in frequency is converted into a digital
quantity in 15 bits by means of the block "Calc. Hz / %", where parameters P248 and P250 define the input signal
frequency band, while parameter P022 shows the frequency of the pulses in Hz.
Function
FI - P246
Gain
FI - P247
Filter
P245
100 (%)
FI(%)
FI(Hz) - P022
FI(Hz)
Calc. Hz / %
(Hz)
P248
P250
Offset
FI - P249
Value FI
(internal)
Signal FI
(via DIx)
Figure 12.4:
Block diagram of frequency input - FI (DIx)
Digital input DIx is pre-defined for frequency input via parameter P246, with operating capacity in a wide band
from 1 to 3000 Hz.
P022 - Value of Frequency Input
Adjustable
Range:
1 to 3000 Hz
Factory
Setting:
Properties:
ro
Description:
Value in hertz of the frequency input FI.
NOTE!
The operation of parameters P022 as well as of the frequency input, depends on the configuration
of the parameter P246.
P245 - Filter of the Frequency Input
Adjustable
Range:
0.00 to 16.00 s
Factory
Setting:
0.00 s
Properties:
Description:
This parameter sets the time constant of the Frequency Input filter. It is intended to attenuate sudden changes
in its value.
Summary of Contents for CFW300 V1.3X
Page 2: ......
Page 8: ...Contents...
Page 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Page 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Page 72: ...V f Scalar Control 9 10 CFW300 9...
Page 80: ...VVW Vector Control 10 8 CFW300 10...
Page 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Page 132: ...Reading Parameters 15 6 CFW300 15...