General Information
2-8 | CFW-11M G2
2
2.5 IDENTIFICATION LABEL FOR THE UP11 G2
The nameplate is located on the front of the UP11 G2.
MOD.: UP11-01 G2
MAT.: 13353741
MAX. TA: 40 ºC (104 °F)
OP.: 8888888888
SERIAL#: 8888888888
PESO/WEIGHT: 94 kg (42,6 lb)
12 0
LINK DC
OUTPUT
SALIDA
SAÍDA
574-970 V DC
0-0,71*VDC
VAC 3~
A (ND)
60s/3s
570 A
496 A
496 A / 744 A
A (HD)
60s/3s
437 A
380 A
570 A / 760 A
758-1150 V DC
0-0,71*VDC
VAC 3~
A (HD)
60s/3s
505 A
439 A
483 A / 744 A
A (HD)
60s/3s
390 A
340 A
570 A / 680 A
Hz
50/60 Hz
0-200 Hz
FABRICADO NO BRASIL
HECHO EN BRASIL
MADE IN BRAZIL
WEG, CP420 - 89256-900
Jaraguá do Sul - Brazil
UP11-01 G2
13353741
SERIAL#: 8888888888
12 0
7
90
932
2
13
88
93
Model of the UP11
WEG part number
Inverter net weight
Rated input data (voltage, rated
currents for operation with normal
duty and heavy duty, frequency)
Current specifications for
operation with normal duty (ND)
Current specifications for
operation with heavy duty (HD)
Manufacturing date (48 corresponds
to the week and H to the year)
Maximum ambient temperature
around the inverter
Rated output data (voltage, number of
phases, rated currents for operation
with normal duty (ND) and heavy duty
(HD), overload currents for 1 min and
3 s and frequency band)
Serial number
Figure 2.6:
UP11 G2 nameplate
Nameplate
Figure 2.7:
Location of the Nameplates