Optional Items and Accessories
7-2 | CFW-11W G2
7
ATTENTION!
The UP11W G2 becomes 120 mm higher with the quick couplings in the coolant inlet and outlet fittings.
ATTENTION!
The addition of quick couplings increases de pressure drop in the UP11W G2 by 1,55 bar. Considering
the 20 l/min flow and the composition of 88,5 % of water, 10 % de glycol and 1,5 % of inhibitor CorteC
VpCI-649 in the coolant.
7.1.2 Safety Stop Function
Inverters with the following coding CFW11WG2...O...Y.... See the
Section 3.3 SAFETY STOP FUNCTION on page
.
7.2 ACCESSORIES
The accessories are installed on the inverters easy and quickly using the “Plug and Play” concept. When an
accessory is connected to the slots, the control circuit identifies the model and informs the code of the accessory
connected in P0027 or P0028. The accessory must be installed with the inverter power supply disconnected.
The code and models available of each accessory are presented in
. They may be ordered
separately and will be shipped in individual packages containing the components and the manuals with detailed
instructions for the product installation, operation and programming.
ATTENTION!
Only one module can be used at a time in each slot 1, 2, 3, 4 or 5.
Table 7.1:
Accessory models
WEG Item
(material
number)
Name
Description
Slot
Identification
Parameters
P0027 P0028
Control Accessories to Install in Slots 1, 2 and 3
11008162
IOA-01
IOA Module: 1 analog 14-bit input in voltage and current; 2 digital inputs; 2
analog 14-bit outputs in voltage and current; 2 open collector digital outputs
1
FD--
----
11008099
IOB-01
IOB Module: 2 isolated analog inputs in voltage and current; 2 digital inputs;
2 isolated analog outputs in voltage and current (same output programming
as the standard CFW-11); 2 open-collector digital outputs
1
FA--
----
11126674
IOC-01
Module with 8 digital inputs and 4 digital relay outputs (use with SoftPLC)
1
C1
----
11126730
IOC-02
Module with 8 digital inputs and 8 NPN open-collector digital outputs (use
with SoftPLC)
1
C5
----
11820111
IOC-03
IOC module with 8 digital inputs and 7 PNP open-collector digital outputs
1
C6
----
11126732
IOE-01
Input module for 5 PTC sensors
1
25--
----
11126735
IOE-02
Input module for 5 PT100 sensors
1
23--
----
11126750
IOE-03
Input module for 5 KTY84 sensors
1
27--
----
11008100
ENC-01
Incremental encoder module, 5 to 12 Vdc, 100 kHz, with repeater of the
encoder signals
2
--C2
----
11008101
ENC-02
Incremental encoder module, 5 to 12 Vdc, 100 kHz
2
--C2
----
11008102
RS485-01
RS-485 serial communication module (Modbus)
3
----
CE--
11008103
RS232-01
RS-232C serial communication module (Modbus)
3
----
CC--
11008104
RS232-02
RS-232C serial communication module with switches to program the
microcontroller flash memory
3
----
CC--
11008105
CAN/RS485-01
CAN and RS-485 interface module (CANopen / DeviceNet / Modbus)
3
----
CA--
11008106
CAN-01
CAN interface module (CANopen / DeviceNet)
3
----
CD--
11045488
PROFIBUS DP-01
Profibus DP communication module
3
----
C9
11008911
PLC11-01
PLC module
1, 2
and 3
----
--xx
(1)(3)