CFW701 | 29
First Time Power-Up and Start-Up
E
ng
lis
h
5.2.1 Oriented Start-up Menu
Step
Action/Display Indication
Step
Action/Display Indication
1
2
Monitoring mode.
Press the
ENTER/MENU
key to get into
the first level of the programming mode.
The
PARAM
group is selected, press the
or
keys to select the
STARTUP
group.
3
4
Press
ENTER/MENU
when the group is
selected.
The parameter
“P0317 – Oriented Start-up”
is then selected, press the
ENTER/MENU
to
get into the parameter content.
5
6
Change the parameter P0317 to
“1 – Yes”
,
by using the
key.
Press
ENTER/MENU
to save.
7
8
In this moment the Oriented Start-up
routine is initiated and the
“CONF”
status
is indicated at the keypad (HMI).
The parameter “P0000 - Access to
Parameters” is selected. Change the
password to set the remaining parameters
if necessary. The factory default is 5.
Press the
key to the next parameter.
If necessary, change “
P0296 – Line Rated
Voltage”
. This change will affect P0151,
P0153, P0185, P0321, P0322, P0323
and P0400.
Press the
key to the next parameter.
9
10
If necessary, change
“P0298 – Application”
parameter. This change will affect P0156,
P0157, P0158, P0401, P0404 and P0410
(this last one only if P0202 = 0, 1 or 2 - V/f
modes). The time and level of the IGBT
overload protection will also be affected.
Press the
key to the next parameter.
If necessary, change “
P0202 – Control
Type”
parameter. This guide will only show
the setting for P0202 = 0 (V/f 60 Hz) or P0202
= 1 (V/f 50 Hz). Refer to the programming
manual for other settings (V/f Adjustable,
V V W or Vector Modes).
Press the
key to the next parameter.