l Analog Voltage Regulator AVR-A-OPT-03
24
18 TERMINAL CONNECTION
E1/E2
: Single-phase sensing voltage.
E3/4
: Power supply voltage and single-phase sensing voltage common connection
3
: Power supply.
: Connection to 5k
/ 3W potentiometer (for external voltage control).
F+ e F-
: Connection to exciter field of the generator.
JHz
: Jumper 50/60 Hz (JHz position 1-2 = 50 Hz
– position 2-3 = 60 Hz).
JR
: Sensing voltage selector Jumper (pins 1-2 = 160 to 300V, pins 2-3 = 320 to 600V).
19 TEST DIAGRAM WITHOUT GENERATOR (AVR-A-OPT-03 / AVR-A-
OPT-03/B)
Below is the connection diagram for bench testing the regulator to verify proper operation of the equipment.
Figure 19.1: Regulator connection without regulator
ATTENTION
1. The lamp voltage must be the same voltage applied on the input. The Figure 19.1 shows an example
using a 220V/100W lamp.
U/F
Stb
Vad
JHz
JR
OK
Lamp of 220V/100W or resistor for
nominal current
Voltage variation 170 up to 250Vca
Imput
220Vac