C CONFIGURATIONS
5 C CONFIGURATIONS
This menu allows the programming of all SSW configuration parameters.
C8 COMMUNICATION
To change information via communication network, the SSW has several standard protocols.
The following necessary accessories and protocols are available:
Protocol
Accessory
Modbus RTU
SSW900-CRS485-W
Profibus DP
SSW900-CPDP-N
DeviceNet
SSW900-CDN-N
EtherNet/IP
SSW900-CETH-IP-N
Modbus TCP
SSW900-CMB-TCP-N
PROFINET IO
SSW900-CPN-IO
For further details regarding the SSW configuration to operate these protocols, refer to the SSW Communication
Manual.
C8.1 I/O Data
Configure network data exchange area.
Use this for cyclic communication over Anybus-CC for Profibus, DeviceNet, EtherNet/IP and PROFINET IO. For
RS485 using Modbus RTU protocol or Anybus-CC Modbus TCP module, a contiguous area of holding registers
(@1500-@1549 and @1600-@1619) can be accessed using standard Modbus functions.
Slot 1
Slot 2
Data write
to
to
word
#
1 = Net Id
word
#
26 = Net Id
word
#
25 = Net Id
word
#
50 = Net Id
1
◦
word = 1
1
◦
word =26
Quantity = 25
Quantity = 25
Data read
to
to
Slot 1
Slot 2
Word
#
1 = Net Id
Word
#
11 = Net Id
Word
#
10 = Net Id
Word
#
20 = Net Id
1
◦
Word = 1
1
◦
Word =11
Quantity = 10
Quantity = 10
{
{
{
{
Figure 5.1:
Example of data setting.
C8.1.1 Data Read
Configure a set of 16 bit parameters to read over the network.
C8.1.1 Data Read
C8.1.1.1 Slot 1 1st Word
Range:
1 ... 50
Default:
1
Properties:
Stopped
Description:
It sets the index of the first programmable read word for data communication (inputs for master).
SSW900 | 15