LX3V-ETH-BD
9
FUZHOU FU CHANG WECON ELECTRONICS TECHNOLOGY CO., LTD.
2) The parameter setting of two devices connected with the LX3V-ETH-BD
3) Send and receive data to two connected devices
Device 1
Device 2
The protocol of device 1: Modbus master
The IP of the slave is 192.168.1.35
Configure Port number as 502
Configure timeout as 100ms
The protocol of device 2: Modbus master
The IP of the slave is 192.168.1.11
Configure Port number as 502
Configure timeout as 100ms
Station number 01, function code 10(write word)
The start address for writing is 1
The length of address is 1
Write the data of D600 to address 1 in device 1
that is connected with Ethernet port 1
Station number 01, function code 0F(write word)
The start address for writing is 2
The length of address is 10
Write 10 data starting from D800 to the 10
address starting from address 2 in device 2 that
is connected with Ethernet port 1
Use the Ethernet port 1, and the parameter
table start from D300 and0 M300