Wecon LX3V-4DA User Manual Download Page 8

                                                                                                                                             

LX3V-4DA module

 

7                                                       

                                                                                  WECON Technology Co., Ltd.

 

Write data in respective data registers while observing the following ranges: 

Data register D0 and D1: -2,000 to +2,000 Data register D2 and D3: 0 to +1,000 

Data register D0→ BFM #1 (output to CH1) 
Data register D1→ BFM #2 (output to CH2) 

Data register D2→ BFM #3 (output to CH3) 

Data register D3→ BFM #4 (output to CH4) 

 

Operation procedure 

1)

 

Turn off the power of the MPU, and then connect the LX3V-4DA. After that, wire the I/O lines of 
the LX3V-4DA. 

2)

 

Set the MPU to STOP, and turn on the power. Write the above program then switch the MPU to 

RUN. 

3)

 

Analog values will be sent from D0 (BFM #1), D1 (BFM #2), D2 (BFM #3), and D3 (BFM #4) to the 
respective  output  channels  of  the  LX3V-4DA.  When  the  MPU  is  in  STOP,  the  analog  values  set 
before stopping the MPU will remain output. (The output will be held); 

4)

 

When the MPU is in STOP, the offset values can also be output. For a detailed description, refer to 
Section 5. 

 

Program example 

For the following program, CH1 and CH2 of the LX3V-4DA connected at special block position No. 1 are 

used as voltage output channels, CH3 as a current output channel (+4 mA to +20 mA), and CH4 as a current 

output channel (0mA to +20 mA). When the MPU is in STOP, the output will be held. In addition, the status 

information is used. 

 

BFM#30  data  (model  code)  of  block  No.1  transferred 
data register D4. 
M1  will  be  tuned  on  when  the  model  code  is  set  to 
K3020 
H2100→ BFM#0 (unit No.1) 
CH1  and  CH2:  Voltage  output;  CH3:  Current  output 
(+4mA to +20mA); CH4: Current output (0 to +20mA) 
D0 → BFM#1 (CH1 output) 
D1 → BFM#2 (CH2 output) 
D2 → BFM#3 (CH3 output) 
D3 → BFM#4 (CH4 output) 
BFM#29 (b15 to b0) → (M25 to M10) 
Reads out the status data 

 

Output data abnormal 
 

Summary of Contents for LX3V-4DA

Page 1: ...oduleV2 Wecon Technology Co Ltd Website http www we con com cn en Technical Support liux we con com cn Skype fcwkkj or Jason chen842 Phone 86 591 87868869 QQ Group 465230233 Technical forum http wecon...

Page 2: ...main unit is by buffer memory exchange There are 32 buffer memories each of 16 bits in the LX3V 4DA The LX3V 4DA consumes 90mA current from the 5V power supply in LX3V main unit or active expansion u...

Page 3: ...refer to section 2 External Dimensions and Parts Figure 3 2 1 Use a twisted pair shielded cable for the analog output This cable should be wired away from power lines or any other lines which could i...

Page 4: ...efault offset value 0 Default gain value 5000 Output mode 0 11 Gain data CH1 2 12 Offset data CH2 1 13 Gain data CH2 2 14 Offset data CH3 1 15 Gain data CH3 2 16 Offset data CH4 1 17 Gain data CH4 2 1...

Page 5: ...0 1000 16uA 4000 20000 1000 2 0 20mA 0 1000 20uA 0 20000 1000 3 Disable 4 10V 10V 10000 10000 1mV 0 5000 5000 5 4mA 20mA 0 2000 8uA 4000 20000 2000 6 0 20mA 0 2000 10uA 0 20000 2000 2 BFM 5 Data holdi...

Page 6: ...n once set will be valid until the Permit command BFM 21 1 is set The initial value is 1 Permit The set value will be retained even after power off 7 BFM 29 Error status When an error occurs use the F...

Page 7: ...A mode change of BFM 0 automatically involves a change of the corresponding offset and gain values Because of the time needed to write the new values to the internal EEPROM memory a delay of 3 s is r...

Page 8: ...e analog values set before stopping the MPU will remain output The output will be held 4 When the MPU is in STOP the offset values can also be output For a detailed description refer to Section 5 Prog...

Page 9: ...n the LX3V MPU or a powered extension unit varies according to the number of extension blocks or special function blocks connected 5 Put the main processing unit into RUN 6 After turning on or off the...

Page 10: ...ment of I O Characteristics To adjust the I O characteristics set the offset and gain of the LX3V 4DA either using push button switches connected to input terminals of the programmable controller or u...

Page 11: ...index 4 n Number of transfer points K1 to K32 K1 to K16 for 32 bit command 2 Write BFM 1 m1 m2 n Same as read BFM 2 S Head device number of source data T C D KnX KnM KnY KnS V Z K and H can be used t...

Page 12: ...h D A conversion are normal On or off The ambient conditions are not suitable for the LX3V 4DA or the LX3V 4DA is defective 5 Check that the external load resistance connected to each analog output te...

Reviews: