Wecon LX3V-2TC-BD Mounting Instruction Download Page 4

                                                                                                                                                     

LX3V-2TC-BD

 

3                                                       

                                                                                  WECON Technology Co., Ltd.

 

Temperature 

Read data by buffers 

Analog input signal 

Thermocouple: K or J type (2 channels) 

Range 

of 

rated 

temperature 

-100

  - 1200

 

-100

  - 600

 

Digital output 

-1000 - 12000 

-1000 - 6000 

12 bits total 

Accuracy 

0.4

   

0.3

 

Overall accuracy 

±0.5% 

Conversion rate 

50ms*2   

Conversion characteristics 

 

Note: Ground-type thermocouple (3-wire) is not supported in this BD module. 

 

5.

 

Wire 

Warning 

Make sure cut off the electricity before installation/disassembly, to prevent electric shock or product 

damages. 
 

Caution

   

1)

 

Stay away from high-voltage cables to avoid interference or surge; 

2)

 

Grounding is required, but please do not share the ground site with high-voltage cable; 

3)

 

Do  not  weld  any  cable  ends,  and  make  ensure  that  the  number  of  connecting  cables,  no  more 

than a predetermined number; 

4)

 

Do not connect a substandard cable; 

5)

 

Fixed cable; 

5.1 Suitable cable 

Use AWG25-16 to connect the output equipment 

The maximal screwing torque is from 0.5 to 0.6N.m 

Table 5-1 

Line type 

Cross sectional area(mm

2

)  End-of-pipe treatment 

 

Summary of Contents for LX3V-2TC-BD

Page 1: ...ON LX3V 2TC BD Module Website http www we con com cn en Technical Support liux we con com cn Skype fcwkkj or Jason chen842 Phone 86 591 87868869 QQ Group 465230233 Technical forum http wecon freeforums net ...

Page 2: ...ead to failure 3 BD module and top cover of PLC s tightening torque is 0 3 0 6 N m Warring Make sure to power off the PLC before mounting or removing the BD module and put the cover in right place 2 Special feature 1 LX3V 2TC BD module equips with 2 channels analog output This module will be mounted in the PLC so there is no need to change the installation area of the PLC 2 The type to AD convert ...

Page 3: ... the measurement range 4 LED4 TC 2 On indicates enable OFF indicates disable flicker indicates exceeding the measurement range If the BD module is plugged into the old firmware version when on the host all LEDs will be flashing 4 Specifications 1 Please refer to the LX3V user manual for the general specification of LX3V 2TC BD 2 LX3V 2TC BD is powered supply by LX3V main unit Table 4 1 Item Explan...

Page 4: ...re cut off the electricity before installation disassembly to prevent electric shock or product damages Caution 1 Stay away from high voltage cables to avoid interference or surge 2 Grounding is required but please do not share the ground site with high voltage cable 3 Do not weld any cable ends and make ensure that the number of connecting cables no more than a predetermined number 4 Do not conne...

Page 5: ...ple input mode and stored value in D0 and D2 6 2 Examples of Applications Since the LX3V 2TC BD does not have offset and gain functions if it needs for the values out of the standard specifications Additional programming orders will be needed to multiply or divide the converted value Caution Since the use of additional programming orders the converted precision and resolution of the analog Set CH1...

Page 6: ...hermocouple input mode In Thermocouple input mode LX3V 2TC BD covert an analog value to a digital value in degrees Celsius If in the program is Fahrenheit as a unit it needs to be converted to Celsius value Fahrenheit and Celsius conversion formula Fahrenheit Celsius 9 5 32 the unit is 0 1 D10 D8112 9 D12 D10 5 D0 D12 320 D0 D8112 9 5 320 ...

Reviews: