Weber SUMMIT GOLD D Dimension Manual Download Page 5

5

1).  At least one ventilation opening (a hole or group of 

holes, for the purpose of ventilation) needs to be on 

one side of the enclosure that communicates with 

the outside of the “island” structure. If a gas leak 

should occur or the LP cylinder should vent in the LP 

cylinder enclosure, the gas should not be allowed to 

vent or migrate into the empty or “hollow” area of the 

“island”.  Ventilation openings should only communi-

cate with the outside of the “island” structure, so that 

the gas can dissipate outside of the “island” structure. 

The ventilation opening should be located within 

5 inches (127mm) of the top of the enclosure, and 

should have a total free area of 20 square inches. 

(This relates to 1 square inch of ventilation area, per 

pound of stored fuel).

2).  At least one ventilation opening (a hole or group of 

holes, for the purpose of ventilation) needs to be on 

one side of the enclosure that communicates with the 

outside of the “island” structure, at the bottom. If a 

gas leak should occur or the LP cylinder should vent 

in the LP cylinder enclosure, the gas should not be 

allowed to vent or migrate into the empty or “hollow” 

area of the “island”.  Ventilation openings should 

only communicate with the outside of the “island” 

structure, so that the gas can dissipate outside of 

the “island” structure. The ventilation opening should 

be located within 5 inches (127mm) of the bottom of 

the enclosure, and should have a total free area of 

10 square inches. (This relates to 1/4 square inch of 

ventilation area, per pound of stored fuel).

3).  The minimum size of the ventilation hole (s) should 

not be less than  inch.

d).  The remote LP cylinder enclosure should be constructed 

with non-combustible materials. The remote LP cylinder 

enclosure should isolate the LP cylinder from the burner 

compartment, so that it provides shielding from radiation, 

be a flame barrier and provide protection from foreign 

material such as hot drippings. 

e).  There should be a minimum of 2 inches (50.8mm) be-

tween the ground and the floor of the remote LP cylinder 

enclosure. 

f).  The LP cylinder valve should be readily accessible for 

hand operation. A door on the remote LP cylinder enclo-

sure to gain access to the LP cylinder valve is acceptable, 

provided it is non- locking and can be opened without the 

use of tools.

If your, licensed contractor or licensed plumber, builds an LP 

cylinder enclosure following the guidelines in the ANSI Stan-

dard for Outdoor Cooking Gas Appliances, 

Z21.58 CSA 1.6, you need to order kit number (#21287), 

which will contain the hose and regulator assembly, mount-

ing bracket for the regulator, connection fittings and LP tank 

bracket for retaining the LP cylinder that must be used with 

the Summit

®

 Built-In gas grill. The hose and regulator in the 

kit (#21287) is listed as part of the CSA listed Summit

®

 Built-

In gas grill.

DANGER

Use of any other hose and regulator assembly could be 

dangerous, and may not provide adequate gas supply 

to the Summit

®

 Built-In gas grill, and could result in a 

fire or an explosion causing serious bodily injury or 

death and damage to property. 

DANGER

Failure to use the the Summit

®

 Built-In Tank Cabinet for 

a 20 lb cylinder or failure to build a LP cylinder enclo-

sure for a 20 lb cylinder following the requirements for 

ventilation, cylinder retention and separation of the LP 

cylinder from a heat source, listed in the ANSI Stan-

dard for Outdoor Cooking Gas Appliances, ANSI Z21.58 

CSA 1.6, could be dangerous, and could result in a fire 

or an explosion causing serious bodily injury or death 

and damage to property.

If you do not follow the DANGER statements exactly, the 

Warranty on the Summit

®

 Built-In gas grill will be voided. 

Reviews: