Self-Priming Pumps.
11
Electric motor & connections.
Read the motor manufacturer’s instructions, or consult the connection
diagram located either on the motor name plate or inside the cover on
the conduit box. The wiring of the motor and control panel, overload
protection and grounding should be in accordance with State, Province,
Local and National Electrical Code (NEC) or Canadian Electrical Code
(CEC). Be sure the following criteria are met:
1. AC power is within ± 10% of rated voltage with rated
frequency. (See motor name plate for rating).
OR
2. AC power is within ± 5% of rated frequency with rated
voltage. OR
3. A combined variation in voltage and frequency of ±10% (sum
of absolute values) of rated values, provided the frequency
variation does not exceed ± 5% of rated frequency.
Pump Lubrication.
The pump requires no lubrication. The impeller and seal are the only
moving parts of the pump. These parts are water lubricated and
need no attention.
5. Operation.
Priming.
Remove the priming plug, located in the top of the discharge tee or in
CAUTION.
Do not operate pump without liquid in pump body
as operating dry will result in damage to the seal.
Summary of Contents for AG Series
Page 1: ...Self Priming Pumps Operation Manual...
Page 15: ...Self Priming Pumps 15 7 Sectional AE Series...
Page 17: ...Self Priming Pumps 17 1 AG AD Series...
Page 19: ...Self Priming Pumps 19 1 AAG AAD...
Page 21: ...Self Priming Pumps 21 1 AU Series Item Description 1 Discharge 2 Suction...
Page 26: ...26 Operation Manual 26 Notes...
Page 27: ...Self Priming Pumps 27 1 Notes...
Page 28: ...Type text 4034 Mint Way Dallas Texas 75237 800 783 6756 214 337 8780 support wdmpumps com...