background image

INSTALLATION MANUAL

8

TROUBLESHOOTING 

(CONTINUED)

Symptoms

Possible Cause(s)

Suggested Remedies

Pump operates 
noisily or vibrates 
excessively

1.  Worn bearings
2.  Impeller broken
3.  Piping attachments to building 

structure too rigid or too loose

1.  Replace pump
2.  Replace pump
3.  Install rubber coupling (available at local hardware stores) to isolate 

pump vibration from discharge plumbing

Pump will not 
shut off

1. Switch
2.  Switch obstructions
3.  Restricted discharge (obstruction in 

piping)

4.  Excessive inflow or pump not 

properly sized for application

1.  Replace switch
2.  Remove obstruction to verify free motion of switch
3.  Remove obstruction from discharge piping

4.  Recheck all sizing calculations to determine proper pump size

Pump operates 
but delivers little 
or no water

1.  Low supply voltage
2.  Inlet clogged
3.  Broken impeller
4.  Pump not properly sized for 

application

5.  Check valve stuck closed or 

installed backwards

6.  Shut off valve closed

1.  Contact an electrician
2.  Remove debris
3.  Replace pump
4.  Recheck all sizing calculations to determine proper pump size

5.  Remove and examine check valve for proper installation and free 

operation

6.  Open valve

ROUTINE MAINTENANCE

The pump should be inspected 3-4 times per year for pump movement or buildup of debris on the switch or floar. Reposition 
pump if it has moved. Remove any debris that could interfere with the operation of the switch. Lack of proper routine maintenance 
will void warranty.

•   Make sure the pump is plugged in to a working ground fault circuit interrupter (GFCI) outlet and the cord is in good shape. In 

damp areas, GFCI breakers may trip, effectively shutting off the effluent pump. Check in on your sewage pump and reset the 
GFCI if necessary.

•  Ensure the pump itself is standing upright. Vibrations during operation can cause it to fall or tilt onto one side. This can jam the 

float arm so it can’t activate the pump.

•  Pour a bucket of water into the pit to make sure the pump starts automatically and the water drains quickly once the pump is 

on. If the pump doesn’t start, have it serviced or replaced.

•  Replace the switch every two (2) years. This maintence will reduce the risk of improper pump operation, switch failure and/or 

flooding.

Summary of Contents for EFL50

Page 1: ... Reinforced Thermoplastic SEL50 EFL50 Glass Reinforced Thermoplastic IMPELLER Glass Reinforced Thermoplastic SHAFT Steel DISCHARGE 2 in NPT Sewage Effluent Pumps PERFORMANCE Model HP Discharge Head 0 ft 5 ft 10 ft 15 ft 20 ft RPP50 1 2 Gal hr 6200 4800 3240 1500 SEL50 1 2 Gal hr 10000 9000 7200 5000 2000 WCS50T 1 2 Gal hr 10000 9600 8000 3300 EFL50 1 2 Gal hr 10000 9000 7200 5000 2000 Intended for...

Page 2: ...que de choc électrique s assurer qu elle est branchée seulement à une prise de courant correctement mise à la terre FOR ADDED SAFETY the receptacle must be protected with a ground fault circuit interrupter GFCI All wiring must be performed by a qualified licensed electrician and comply with the National Electric Code and all applicable local codes and ordinances POUR PLUS DE SÉCURITÉ la prise de c...

Page 3: ...ACHEMINEMENT D EAU DESTINÉE À LA CONSOMMATION Ne pas utiliser la pompe pour transporter de l eau qui sera utilisée comme de l eau potable destinée à la consommation La pompe doit être utilisée uniquement dans les applications pour lesquelles elle est conçue DO NOT USE AN EXTENSION CORD OR SURGE PROTECTOR Extension cords and or surge protectors could present a safety hazard if not sized properly be...

Page 4: ...P SHOULD BE USED when risk of property damage from high water levels exists UNE ALARME AUTONOME DE NIVEAU D EAU ÉLEVÉ OU UNE POMPE DE SAUVEGARDE DOIVENT ÊTRE UTILISÉES en cas de risque de dégâts matériels causés par des niveaux d eau élevés REPLACE THE SWTICH EVERY T WO 2 YEARS This maintenance will reduce the risk of improper pump operation switch failure and or flooding REMPLACER LE COMMUTATEUR ...

Page 5: ...structions 6 Install discharge plumbing according to local regional and state codes Do not reduce the discharge pipe size below that which is provided on the pump 7 If optional control device or float is used follow mounting instruction supplied with device or float 8 A union should be installed above the basin to allow easy removal of the pump for cleaning and service 9 Install a check valve requ...

Page 6: ...ould be installed above the check valve as required by local regional or state codes 10 Connect remaining discharge pipe The remainder of the discharge line should be as short as possible with a minimum number of turns 11 Secure power supply cord to discharge pipe using cable or zip ties to prevent possible switch entanglement 12 Connect pump power supply cord to a ground fault circuit interrupter...

Page 7: ...of switch 3 Remove obstruction in discharge piping 4 Contact an electrician TROUBLESHOOTING WARNINGS ALWAYS DISCONNECT THE PUMP FROM POWER SUPPLY before installing servicing or making any adjustments TOUJOURS METTRE LA POMPE HORS TENSION avant de procéder à l installation à l entretien ou à des réglages LET PUMP COOL FOR A MINIMUM OF 2 HOURS BEFORE ATTEMPTING TO SERVICE Submersible pumps contain o...

Page 8: ...mp 4 Recheck all sizing calculations to determine proper pump size 5 Remove and examine check valve for proper installation and free operation 6 Open valve ROUTINE MAINTENANCE The pump should be inspected 3 4 times per year for pump movement or buildup of debris on the switch or floar Reposition pump if it has moved Remove any debris that could interfere with the operation of the switch Lack of pr...

Page 9: ...ARRANTY SERVICE PARTS SHEET REPLACEMENT PARTS REPAIR KITS REF NO DESCRIPTION MODELS Sewage RPP50 SEL50 WCS50T Effluent EFL50 1 TETHER SWITCH ALL MODELS 56835 WYN1 2 10 FT CORD WCS50T ONLY 31006 WYN2 9 2 ...

Page 10: ...is Limited Warranty does not cover Products which have been damaged as a result of accident abuse misuse neglect improper installation improper maintenance or failure to operate in accordance with Wayne Water Systems written instructions THIS WARRANTY IS IN LIEU OF ANY AND ALL OTHER WARRANTIES OBLIGATIONS OR AGREEMENTS EXPRESSED OR IMPLIED INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNE...

Page 11: ..._ _____________________________________________________________________________________________ _____________________________________________________________________________________________ _____________________________________________________________________________________________ _____________________________________________________________________________________________ ______________________...

Page 12: ...12 www waynepumps com ...

Reviews: