Wavetek 801 Instruction Manual Download Page 7

respect to its sync pulse. These pulse parameters are shown

in figure 3-2. Specific setups for each mode are given in
paragraph 3.3.

3.2.1 

White Marks

When first becoming familiar with the 801, the white mark
settings are handy. The white mark settings for the front

panel switches will always give a 5k to 50 kHz  sync signal

when power is on. The same settings will give 50% duty
time, TTL, ECL, ECL and 

 OUT pulses; the LOWER

LEVEL/UPPER LEVEL control may need adjusting to ob-

serve the 

 OUT on an oscilloscope. Once the output is

observed, each control can be adjusted and observed until
the desired result is obtained.

3.2.2 

Pulse Width, Transition and Delay

Narrow duty cycle pulses require the NORMAL OUTPUT

while greater than 70% duty cycle pulses require the COMP
OUTPUT setting. Pulse width plus trailing edge time plus
delay time settings should not exceed the period time. (See
figure 3-2.) The sum of width, trailing edge and delay actu-
ally must be somewhat less than period time by an amount
that depends upon the period time selected. Therefore,

when the sum of the desired width, trailing edge and delay
time exceeds 70% of the period time, the pulse should be
observed to make sure it is as desired.

The 50% duty time width setting 

 )

 is meant to be used

in continuous mode. Other modes result in the following
default conditions.

Mode Selected output

TRIG 

A triggered 10 ns pulse

CONT 

A continuous output of paired 10 ns pulses

TRIG 

A triggered output of paired 10 ns pulses

GATE 

A gated output of paired 10 ns pulses

3.2.4 

Output Terminations

Only 

 RG58U  cable should be used to connect the 801

to the circuit under test. A 

 2W load should be used at

the circuit end of the cable for maximum pulse fidelity.

The 

 terminations should always be used on the SYNC

and TTL outputs and 

 Thevenin loads should be used

on the ECL outputs.

3.2.5 

Nonlinear and Reactive Loads

Both nonlinear and reactive loads will cause pulse distortion.
Reactive loads driven with fast transitions cause voltage

spikes that can damage the 801 output amplifier. If it is
necessary to drive reactive loads directly, the instrument
must be protected against these voltage spikes.

3.2.6 

Duty Cycle

Always use the lowest range possible for both delay and
width functions. This will reduce the recovery time of the
one-shots and extend the maximum duty cycle of the 801
to its fullest capability.

3.2.7 

Output Mixing

The outputs of two 801’s may be mixed using the following
network.

 MIXED OUTPUT

FROM

FIRST 801

OUTPUT

FROM

SECOND 801

OUTPUT

3.2.3 ECL 

Termination

Maximum output from either generator is limited to 6 volts.

Figure 3-3 shows a 5.2/0volt  

 ECL termination. Similar

 terminations can be made for ECL circuits with other

voltage arrangements.

801

-5.2V

ECL

ECL CIRCUIT

3 FT RG58U COAX

 OR EQUIVALENT

Figure 3-3. ECL Termination

3.2.8 

Precise Output Levels

Many times when testing a circuit it is desirable to lock the
output of the generator at either the high or low level. A
precise measurement of this level may then be obtained
using a DVM.

The external width 

mode is useful for this purpose. 

Set the

MODE to EXT WIDTH, TRIGGER to 

 and TRIGGER

LEVEL maximum cw. The output will now be locked to

the 

lower 

level. Switching the trigger to 

 will lock it to

the upper level.

3-4

Summary of Contents for 801

Page 1: ...O PRIETARY TO WAVETEK THE INFORMATION IN THIS DOCUMENT IS NOTTOBE USEDFOR DUPLICATED IN ANY MANNER WITHOUT THE PRIOR APPROVAL IN WRITING OF WAVETEK SAN DIEGO 9045 Balboa Ave San Diego Calif 92123 P 0...

Page 2: ...er of pulses may be triggered for a burst output Manual and external triggering is indicated by an LED on the front panel for rapid visual set of trigger level Trigger Burst External trigger starts in...

Page 3: ...rigger and external width modes in which case it is deter mined by the trigger signal Transition Time For variable amplitude pulse only Independently adjustable leading and trailing edges from less th...

Page 4: ...ger edge appears see then pulses occur until the trigger signal transverses the generator trigger level again EXT WIDTH DC level at all outputs until a suitable trigger appears see then a pulse occurs...

Page 5: ...OUT 50 DUTY TIME WHEN TRIGGERING IS INTERNAL I I N DELAY LEADING EDGE 1 TRANSITION TIME I I b WIDTH B F WIDTH e UPPER LEVEL TRAILING EDGE TRANSITION TIME LOWER L E V E L LOWER L E V E L J UPPER LEVE N...

Page 6: ...escribed in paragraph 3 1 under the erator Pulses from this output may be controlled in mode switch The pulse itself may be shaped in width level and transition time as well as frequency and leading a...

Page 7: ...Terminations Only 5OQ RG58U cable should be used to connect the 801 to the circuit under test A 5OQ 2W load should be used at the circuit end of the cable for maximum pulse fidelity The 5Oa terminati...

Page 8: ...criptions of operation observe the pulse on an oscilloscope When the 5Oa OUT pulse is not desired disregard leading and trailing edge adjustments See figure 3 2 for pulse parameters 3 3 1 Continuous P...

Page 9: ...ulse Period 3 3 7 Continuous Double Pulses For continuous double pulses set the controls as follows Control MODE OUTPUT Operation CONT DBL NORM or COMP if inverted pulse is desired WIDTH DELAY Set as...

Reviews: