FACTORY PRE-SET OPERATION

Sensor Parameters

T-DELAY

Time Delay 

20 minutes

Passive Infrared Sensitivity

90%

WT

Walk-Through

OFF

Load Parameters

Load 1

 

Loads 2-8 

or more

**

  

 

Plug Load

ON Mode

Operation*

AUTO-

ON

MANUAL-ON 

if switch is used.

AUTO-ON 

if switch is not used.

 AUTO-ON

Blink Warning

OFF

OFF

OFF

Daylighting

ON

OFF

OFF

NOTE: 

*Auto-OFF is enabled according to the sensor Time Delay when a sensor is bound to the load, regardless of whether the load 

was turned on automatically with occupancy or manually using a switch. 

** Max 8 loads using LMRC-100 series room controllers.

TROUBLESHOOTING

Loads do not operate as expected.

LEDs don’t 

light, display 

is off

1.  Check to see that the sensor is connected to the DLM local Network.
2.  Check for 24VDC input to the sensor: Plug in a different DLM device at the sensor location. If the device does 

not power up, 24VDC is not present.
•  Check the high voltage connections to the room controller.
•  If high voltage connections are good and high voltage is present, recheck DLM local Network connections 

between the sensor and the room controller.

The wrong 

lights are 

controlled

Configure the sensor to control the desired lights using the Push n’ Learn adjustment procedure.

LEDs turn ON 

and OFF but 

load doesn’t 

switch

1.  Make sure device is not in PnL.
2.  Check load connections to room controller.

Summary of Contents for LMPX-100-4

Page 1: ...ax Environment For Indoor Use Only Operating Temperature 32 to 131 F 0 to 55 C Storage Temperature 23 to 176 F 5 to 80 C Relative Humidity 5 to 95 non condensing Patent Pending This unit is pre set for Plug n Go operation adjustment is optional For full operational details adjustment and more features of the product see the DLM System Installation Guide provided with Wattstopper room controllers a...

Page 2: ...or DLM Local Network Low Voltage LMRJ Cables Loads 2 1 Line Hot Black wire Neutral White wire Red wire to Load A 1 Yellow wire to Load B 2 LMRC 102 MOUNTING WARNING Do Not Install To Cover a Junction Box Having Class 1 3 or Power and Lighting Circuits Through Ceiling Tile Through Wall Mounting plate Ceiling Hole 0 825 20 9mm dia Stem Base Swivel bracket Occupancy Sensor Ceiling Mounting plate Snug...

Page 3: ...ontrollers TROUBLESHOOTING Loads do not operate as expected LEDs don t light display is off 1 Check to see that the sensor is connected to the DLM local Network 2 Check for 24VDC input to the sensor Plug in a different DLM device at the sensor location If the device does not power up 24VDC is not present Check the high voltage connections to the room controller If high voltage connections are good...

Page 4: ...éfauts de matériaux et de fabrication pour une période de cinq 5 ans Wattstopper ne peut être tenu responsable de tout dommage consécutif causé par ou lié à l utilisation ou à la performance de ce produit ou tout autre dommage indirect lié à la perte de propriété de revenus ou de profits ou aux coûts d enlèvement d installation ou de réinstallation Wattstopper garantiza que sus productos están lib...

Reviews: