3
FACTORY PRE-SET OPERATION
Sensor Parameters
T-DELAY
Time Delay
20 minutes
Passive Infrared Sensitivity
90%
WT
Walk-Through
OFF
Load Parameters
Load 1
Loads 2-8
or more
**
Plug Load
ON Mode
Operation*
AUTO-
ON
MANUAL-ON
if switch is used.
AUTO-ON
if switch is not used.
AUTO-ON
Blink Warning
OFF
OFF
OFF
Daylighting
ON
OFF
OFF
NOTE:
*Auto-OFF is enabled according to the sensor Time Delay when a sensor is bound to the load, regardless of whether the load
was turned on automatically with occupancy or manually using a switch.
** Max 8 loads using LMRC-100 series room controllers.
TROUBLESHOOTING
Loads do not operate as expected.
LEDs don’t
light, display
is off
1. Check to see that the sensor is connected to the DLM local Network.
2. Check for 24VDC input to the sensor: Plug in a different DLM device at the sensor location. If the device does
not power up, 24VDC is not present.
• Check the high voltage connections to the room controller.
• If high voltage connections are good and high voltage is present, recheck DLM local Network connections
between the sensor and the room controller.
The wrong
lights are
controlled
Configure the sensor to control the desired lights using the Push n’ Learn adjustment procedure.
LEDs turn ON
and OFF but
load doesn’t
switch
1. Make sure device is not in PnL.
2. Check load connections to room controller.