UNIT ADJUSTMENT ‑ PUSH n’ LEARN (PnL)

Load Selection Procedure

A configuration button (Config) allows access to our 

patented Push n’ Learn™ technology to change binding 

relationships between sensors, switches and loads .

Step 1: Enter Push n’ Learn

 

Press and hold the Config button (on 

any DLM device) for 3 seconds. 

 

 

The red LED on the LMPL-201 

begins to blink . When you release 

the button, the red LEDs on other 

communicating devices connected 

to the DLM Local Network begin to 

blink . They continue to blink until you 

exit PnL mode .

 

All loads in the room turn OFF immediately after 

entering PnL, then one load will turn ON . This is Load 

#1, which is bound to all occupancy sensors on the DLM 

local network as part of the  Plug n’ Go factory default 

setting . 

All switch buttons and sensors that are bound 

to this load have their blue LED solid ON.

6/2011

14100r1

Please 

Recycle

2800 De La Cruz Blvd .  

Santa Clara, CA 95050 

Phone: 800 .879 .8585 

www .wattstopper .com

PLUG n’ GO OPERATION (PnG)

The plug load circuit connected to the LMPL-201 is 

automatically controlled by all occupancy sensors on the 

DLM local network . After the last occupancy sensor’s 

time delay expires, the LMPL-201 shuts OFF the switched 

receptacle circuit . 

Load Control Arbitration

To take full advantage of automatic PnG configuration, 

review these simple rules about load control arbitration . 
After the room controllers are connected to the DLM Local 

Network and powered up they automatically negotiate to 

determine which controller becomes the Master and the 

load numbers for each relay on the DLM Local Network .
The 

Master

 is the controller with the highest serial number . 

The LMPL-201 has one load relay . 

TROUBLESHOOTING

LEDs on a switch or 

sensor don’t light

1 .  Check to see that the the device is connected to the DLM Local Network .
2 .  Check for 24VDC input to the device: Plug in a different DLM device at the device location . If 

the device does not power up, 24VDC is not present .
•  Check the high voltage connections to the room controller and/or plug load controller(s).
•  If high voltage connections are good and high voltage is present, recheck DLM Local 

Network connections between the device and the room controller(s) .

The wrong lights and plug 

loads are controlled

1 .  Configure the switch buttons and sensors to control the desired loads using the Push n’ 

Learn adjustment procedure . 

LEDs turn ON and OFF but 

load doesn’t switch

1 .  Make sure the DLM local network is not in PnL .
2 .  Check load connections to room controllers and/or plug load controllers .

Config button & 

red LED

Step 2: Load selection

 

Press and release the Config button to step through 

the loads connected to the DLM Local Network . As 

each load turns ON note the devices (switch buttons 

and sensors) that are showing a bright solid blue LED . 

These devices are currently bound to the load that is 

ON . The blue LED on the room controller or plug load 

controller connected to the load is also lit .
•  To 

unbind

 a switch button from a load, press the 

switch button while its blue LED is ON bright . The 

blue LED goes dim to indicate the button no longer 

controls the load that is currently ON .

•  To 

unbind

 an occupancy sensor, press the up (

)

 

or 

down (

) adjustment button while its blue LED is 

ON . The blue LED turns OFF to indicate the sensor no 

longer controls the load that is currently ON . 

 

Pressing the switch button or sensor up (

)

 

or down 

(

) again while the load is ON 

rebinds

 the load to the 

button or sensor and the blue LED illuminates brightly .

Step 3: Exit Push n’ Learn

 

Press and hold the Config button until the red LED turns 

OFF, approximately 3 seconds .

 

Load A ON/OFF button

Blue LED ON when switched 

receptacle circuit is ON .

Load button: 

Press & release to turn the 

switched receptacle ON/OFF .

0341373638

Serial 

Number

Room

Controller

Load

Control

LMPL-201

0429928526

Master

0341373638

LMPL-201

1

0429817004

2

In a DLM local network 

with only LMPL-201 plug 

load room controllers, the 

LMPL-201 with the highest 

serial number is the  

Master, carrying Load 1 . 

The next highest serial 

number would have Load 2 

and so forth .