UNIT ADJUSTMENT ‑ PUSH n’ LEARN (PnL)
Load Selection Procedure
A configuration button (Config) allows access to our
patented Push n’ Learn™ technology to change binding
relationships between sensors, switches and loads .
Step 1: Enter Push n’ Learn
Press and hold the Config button (on
any DLM device) for 3 seconds.
The red LED on the LMPL-201
begins to blink . When you release
the button, the red LEDs on other
communicating devices connected
to the DLM Local Network begin to
blink . They continue to blink until you
exit PnL mode .
All loads in the room turn OFF immediately after
entering PnL, then one load will turn ON . This is Load
#1, which is bound to all occupancy sensors on the DLM
local network as part of the Plug n’ Go factory default
setting .
All switch buttons and sensors that are bound
to this load have their blue LED solid ON.
6/2011
14100r1
Please
Recycle
2800 De La Cruz Blvd .
Santa Clara, CA 95050
Phone: 800 .879 .8585
www .wattstopper .com
PLUG n’ GO OPERATION (PnG)
The plug load circuit connected to the LMPL-201 is
automatically controlled by all occupancy sensors on the
DLM local network . After the last occupancy sensor’s
time delay expires, the LMPL-201 shuts OFF the switched
receptacle circuit .
Load Control Arbitration
To take full advantage of automatic PnG configuration,
review these simple rules about load control arbitration .
After the room controllers are connected to the DLM Local
Network and powered up they automatically negotiate to
determine which controller becomes the Master and the
load numbers for each relay on the DLM Local Network .
The
Master
is the controller with the highest serial number .
The LMPL-201 has one load relay .
TROUBLESHOOTING
LEDs on a switch or
sensor don’t light
1 . Check to see that the the device is connected to the DLM Local Network .
2 . Check for 24VDC input to the device: Plug in a different DLM device at the device location . If
the device does not power up, 24VDC is not present .
• Check the high voltage connections to the room controller and/or plug load controller(s).
• If high voltage connections are good and high voltage is present, recheck DLM Local
Network connections between the device and the room controller(s) .
The wrong lights and plug
loads are controlled
1 . Configure the switch buttons and sensors to control the desired loads using the Push n’
Learn adjustment procedure .
LEDs turn ON and OFF but
load doesn’t switch
1 . Make sure the DLM local network is not in PnL .
2 . Check load connections to room controllers and/or plug load controllers .
Config button &
red LED
Step 2: Load selection
Press and release the Config button to step through
the loads connected to the DLM Local Network . As
each load turns ON note the devices (switch buttons
and sensors) that are showing a bright solid blue LED .
These devices are currently bound to the load that is
ON . The blue LED on the room controller or plug load
controller connected to the load is also lit .
• To
unbind
a switch button from a load, press the
switch button while its blue LED is ON bright . The
blue LED goes dim to indicate the button no longer
controls the load that is currently ON .
• To
unbind
an occupancy sensor, press the up (
)
or
down (
) adjustment button while its blue LED is
ON . The blue LED turns OFF to indicate the sensor no
longer controls the load that is currently ON .
Pressing the switch button or sensor up (
)
or down
(
) again while the load is ON
rebinds
the load to the
button or sensor and the blue LED illuminates brightly .
Step 3: Exit Push n’ Learn
Press and hold the Config button until the red LED turns
OFF, approximately 3 seconds .
Load A ON/OFF button
Blue LED ON when switched
receptacle circuit is ON .
Load button:
Press & release to turn the
switched receptacle ON/OFF .
0341373638
Serial
Number
Room
Controller
Load
Control
LMPL-201
0429928526
Master
0341373638
LMPL-201
1
0429817004
2
In a DLM local network
with only LMPL-201 plug
load room controllers, the
LMPL-201 with the highest
serial number is the
Master, carrying Load 1 .
The next highest serial
number would have Load 2
and so forth .