Switch
Ceiling Mount
Occupancy
Sensor
Room
Controller
J-Box
Line Voltage
(Class 1 wiring)
To Plug Load
(Class 1 wiring)
To Lighting
Load
(Class 1 wiring)
To Other
Electrical
Outlets
Line Voltage
(Class 1 wiring)
Plug Load
Controller
J-Box
LMPL-201
Digital Lighting Management (DLM)
Enhanced Digital Single Relay
Plug Load Room Controller
Quick St
art Guide
Switch
Ceiling Mount
Occupancy
Sensor
Plug Load
Controller
Line Voltage
(Class 1 wiring)
To Plug Load
(Class 1 wiring)
J-Box
To Other
Electrical
Outlets
PLACEMENT EXAMPLES
Input Voltage: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120VAC, 50/60Hz
Load Rating:
Maximum Duplex Receptacle Rating . . . . . . . . . . . . .120VAC, 20A
Class 2 Output to DLM Local Network . . . . . . up to 250mA @ 24VDC
DLM Local Network Characteristics when using LMPL-201:
Provides low voltage power over Cat 5e cable (LMRJ);
max current 800mA . Supports up to 64 load addresses, 48
communicating devices including up to 4 LMRC-10x series and/
or LMPL-101 and/or LMPL-201 controllers . Free topology up to
1,000’ max .
Environment:
Operating Temperature . . . . . . . . . . . . . .32° to 158°F (0° to 70°C)
Storage Temperature . . . . . . . . . . . . . .23° to 176°F (-5° to 80°C)
Relative Humidity . . . . . . . . . . . . . . . . . 5 to 95% (non condensing)
THIS UNIT IS SET FOR
PLUG n’ GO
™
OPERATION,
ADJUSTMENT IS
OPTIONAL.
For full operational details
see the DLM Dimming
System Installation
Guide provided with the
room controller and also
available at
www.wattstopper.com
FOR CONNECTION TO
PLUG LOADS ONLY.
INSTALLATION SHALL BE
IN ACCORDANCE WITH ALL
APPLICABLE REGULATIONS,
LOCAL AND NEC CODES.
Wire connections shall be rated
suitable for the wire size (lead
and building wiring) employed .
MOUNTING THE
CONTROLLER
The plug load room
controller mounts as the
cover for a four square deep
junction box . It is equipped
with a lash and hook to hang
the controller from a j-box
cover tab while connecting the line voltage
wires . After securely connecting the wires,
unhook the lash from the j-box and secure
the controller to the j-box cover tabs using
two screws .
Use a 4”x 4”x 2
1
/
8
deep (minimum) box
ATTACHING LMRJ LOW VOLTAGE CABLES
Remove rubber jack covers to use RJ45 receptacles .
Leave covers in place for all unused receptacles .
WARNING:
TO CONNECT A COMPUTER TO THE
DLM LOCAL NETWORK USE THE
LMCI‑100.
NEVER CONNECT THE DLM
LOCAL NETWORK TO AN ETHERNET
PORT
– IT MAY DAMAGE COMPUTERS
AND OTHER CONNECTED EQUIPMENT.
CAUTION:
TURN THE
POWER OFF AT THE CIRCUIT
BREAKER BEFORE WIRING.
CONNECTIVITY
The LMPL-201 communicates to all other
DLM devices connected to the DLM Local
Network . Connections shown are for
example only . The low voltage LMRJ cables
can connect to any DLM device with an open
RJ45 receptacle .
All line voltage wiring is #12 AWG .
xxxxxr1
www.wattstopper.com • 800.879.8585
120VAC, 50/60Hz
Class 2 Output: 24VDC, 250mA
Maximum Duplex Receptacle Load:
Rating: 120VAC, 20A
For Plug Loads only
Maximum combined load: 20A
UL 2043 Plenum Rated
Enhanced Digital Single Relay
Plug Load Room Controller
APPLIANCE
CONTROL
88T9
LMPL-201
Patent Pending
For Class 2 DLM devices and device wiring:
To be connected to a Class 2 power
source only .
Do not reclassify and install as Class 1,
or Power and Lighting Wiring .
WARNING:
Do not install to cover a
junction box having Class 1, 3 or Power
and Lighting Circuits .
Line
Voltage
Plug Load
Controller
Deep J-Box
Room Controller
Dimmer
Switch
Corner Mount
Sensor
Ceiling Mount
Sensor
DLM Local Network
Low Voltage
LMRJ Cables
LMPL or
LMRC series
Loads
Red wire to Switched Receptacle
Line/Hot
Black wire
Neutral
White wire
Earth Ground/Green wire
Switched
Receptacle
Black wire w/white stripe to Unswitched Receptacle
Unswitched
Receptacle
Ground
Ground
Hook
Lash
4-square
deep
J-box
Hook
Lash