wattstopper LMPL-101 Quick Start Manual Download Page 2

3/2010 

11579

r1

Please 

Recycle

2800 De La Cruz Blvd. 

Santa Clara, CA 95050

Phone: 800.879.8585

www.wattstopper.com

PLUG n’ GO OPERATION (PnG)

The plug load circuit connected to the LMPL-101 is automatically controlled 
by all occupancy sensors on the DLM local network. After the last occupancy 
sensor’s time delay expires or when a switch button bound to the LMPL-100 is 
operated, the LMPL-101 shuts off the plug load circuit. 

TROUBLESHOOTING

Loads do not operate as expected.

LEDs on a switch or 
sensor don’t light

1.  Check to see that the the device is connected to the DLM local network.

2.  Check for 24VDC input to the device: Plug in a different DLM device at the device location. If 

the device does not power up, 24VDC is not present.

•  Check the high voltage connections to the plug load controller.
•  If high voltage connections are good and high voltage is present, recheck DLM local 

network connections between the device and the plug load controller.

The wrong lights and plug 
loads are controlled

1.  Configure the switch buttons and sensors to control the desired loads using the Push n’ 

Learn adjustment procedure. 

LEDs turn ON and OFF but 
load doesn’t switch

1.  Make sure device is not in PnL.

2.  Check load connections to room controllers and/or plug load controllers.

 

Load ON/OFF button

Blue LED ON when 

load is ON

Config button & 

red LED

UNIT ADJUSTMENT - PUSH n’ LEARN (PnL)

Load Selection Procedure

Before testing or adjusting the DLM local network load 
configuration, plug a lamp or radio into one of the electrical 
outlets on the controlled plug load circuit. 

A configuration button (Config) allows access to our 
patented Push n’ Learn™ technology to change binding 
relationships between sensors, switches and loads.

Step 1: Enter Push n’ Learn

 

Press and hold the Config button 
(on any DLM device) for 3 seconds. 

 

 

The red LED on the LMPL-101 
begins to blink faster (2x per 
second) as does the red LED on 
ALL other communicating devices 
connected to the DLM local network. 

 

The red LEDs continue to blink until you exit PnL mode.

 

All loads in the room turn OFF immediately after 
entering PnL, then one load will turn ON. This is Load 
#1, which is bound to switch button #1 and occupancy 
sensors as part of the  Plug n’ Go factory default setting. 

All switch buttons and sensors that are bound to this 
load have their blue LED solid ON.

Step 2: Load selection

 

Press and release the Config button to step through the 
loads connected to the DLM local network. As each load 
turns ON note the devices (switch buttons and sensors) 
that are showing a bright solid blue LED. These devices 
are currently bound to the load that is ON. The blue LED 
on the room controller or plug load controller connected 
to the load is also lit.

• To 

unbind

 a switch button from a load, press the 

switch button while its blue LED is ON bright. The 
blue LED goes dim to indicate the button no longer 
controls the load that is currently ON.

• To 

unbind

 an occupancy sensor, press the up (

)

or 

down (

) adjustment button while its blue LED is 

ON. The blue LED turns OFF to indicate the sensor no 
longer controls the load that is currently ON. 

 

Pressing the switch or up (

)

or down (

) button again 

while the load is ON 

rebinds

 the load to the button or 

sensor and the blue LED illuminates brightly.

Step 3: Exit Push n’ Learn

 

Press and hold the Config button until the red LED turns 
OFF, approximately 3 seconds.

Reviews: