wattstopper LMPL-101 Quick Start Manual Download Page 1

Switch

Ceiling Mount

Occupancy

Sensor

Plug Load
Controller

Line Voltage

(Class 1 wiring)

To Plug Load
(Class 1 wiring)

J-Box 

To Other

Electrical

Outlets

LMPL-101

Digital Lighting Management (DLM)

Digital Plug Load Room Controller

Input Voltage:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120VAC, 50/60Hz

Load Requirements:
 

Maximum Duplex Receptacle Rating . . . . . . . . . . . . . 120VAC, 20A

Output    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .150mA @ 24VDC

DLM Local Network Characteristics for LMPL-101 or LMRC-10x:
 

Provides 24VDC power over Cat 5e cable and RJ-45 connectors

 

Supports up to 24 communicating devices, including 4 

 

LMRC-10x or LMPL-101 controllers

 

Free topology up to 1,000ft of low voltage cable

Environment:
 

Operating Temperature. . . . . . . . . . . . . .32° to 104°F (0° to 40°C)

 

Storage Temperature  . . . . . . . . . . . . . . 23° to 176°F (-5° to 80°C)

 

Relative Humidity. . . . . . . . . . . . . . . . . 5 to 95% (non condensing)

Patent Pending

Quick Start GuideQuick Start Guide

CONNECTIVITY

The LMPL-101 communicates with all other DLM devices 
connected to the DLM local network. Connection drawings 
are for example only. The low voltage LMRJ cables can 
connect to any DLM device with an open RJ45 receptacle.

All line voltage wiring is #12 AWG.

Line

Voltage

Room

Controller

Switch

Ceiling Mount

Sensor

Low Voltage

DLM Local Network

LMRJ Cables

Plug Load

Controller

LMPL-101

J-Box

120VAC

J-Box

Loads

2

1

White: Neutral

Yellow to 

Load 2 (B)

LMRC

102

Red: Switched

120VAC Line

Red to 

Load 1 (A)

Ground

Switch

Ceiling Mount

Occupancy

Sensor

Room
Controller

J-Box 

Plug Load
Controller

Line Voltage

(Class 1 wiring)

To Plug Load
(Class 1 wiring)

J-Box 

To Lighting
Load
(Class 1 wiring)

To Other

Electrical

Outlets

Line Voltage

(Class 1 wiring)

PLACEMENT EXAMPLES

ATTACHING CABLES

MOUNTING THE CONTROLLER

The LMPL-101 controller can either be mounted external to 
a junction box, placing it in the plenum space or mounted 
directly inside a 4” x 4” junction box. 

  Outside a 4” x 4” box                         Inside a 4” x 4” box                                            

Remove rubber jack covers if using all 3 RJ45 receptacles. 
Leave covers in place for all unused receptacles.

WARNING:

 TO CONNECT A COMPUTER TO THE DLM LOCAL 

NETWORK USE THE LMCI-100.  

NEVER CONNECT THE DLM 

LOCAL NETWORK TO AN ETHERNET PORT

 – IT MAY DAMAGE 

COMPUTERS AND OTHER CONNECTED EQUIPMENT.

Line

J-Box

Load

J-Box

Load

Line

THIS UNIT IS PRE-SET FOR PLUG n’ GO™ 

OPERATION, ADJUSTMENT IS OPTIONAL.

For full operational details, adjustment and more 

features of the product, see the DLM System Installation 

Guide provided with the LMRC-102 room controller, 

and also available at 

www.wattstopper.com 

FOR CONNECTION TO PLUG LOADS ONLY.

 

INSTALLATION SHALL BE IN ACCORDANCE WITH ALL 

APPLICABLE REGULATIONS, LOCAL AND NEC CODES.

Wire connections shall be rated suitable for the wire 

size (lead and building wiring) employed.

For Class 2 DLM devices and device wiring:

 

To be connected to a Class 2 power source only. 

 

Do not reclassify and install as Class 1, or Power and Lighting Wiring.

 WARNING:

 Do not install to cover a junction box having Class 1, 3 or 

Power and Lighting Circuits.