background image

6/19/2009 

11589

r1

Please 

Recycle

2800 De La Cruz Blvd .  

Santa Clara, CA 95050 

Phone: 800 .879 .8585 

www .wattstopper .com

PLUG n’ GO OPERATION (PnG)

Plug n’ Go supports the most energy efficient control 

strategy .  For example, if at least two loads, one switch 

and one occupancy sensor are connected to the DLM local 

network, the system operates load A as Automatic ON, 

Automatic OFF and load B as Manual‑On, Automatic‑Off . 
See DLM device Quick Start Guides to determine how each 

device affects the PNG operation of the LMRC‑102 .

Load Control Arbitration

To take full advantage of automatic PnG configuration, 

review these simple rules about load control arbitration . 
After the room controllers are connected to the DLM Local 

Network and powered up they automatically negotiate to 

determine which controller becomes the Master and the 

load numbers for each relay on the DLM Local Network .
The 

Master

 is the controller with the most load relays . If 

more than one controller has the most relays, the one with 

the highest serial number becomes the Master .

TROUBLESHOOTING

Loads do not operate as expected.

LEDs on a switch or 

sensor don’t light

1 .  Check to see that the the device is connected to the DLM Local Network .
2 .  Check for 24VDC input to the device: Plug in a different DLM device at the device location . If 

the device does not power up, 24VDC is not present .

•  Check the high voltage connections to the room controller and/or plug load controller(s).
•  If high voltage connections are good and high voltage is present, recheck DLM Local 

Network connections between the device and the room controller and/or plug load 

controller(s) .

The wrong lights and plug 

loads are controlled

1 .  Configure the switch buttons and sensors to control the desired loads using the Push n’ 

Learn adjustment procedure . 

LEDs turn ON and OFF but 

load doesn’t switch

1 .  Make sure the DLM local network is not in PnL .
2 .  Check load connections to room controllers and/or plug load controllers .

Config button &  

red LED

UNIT ADJUSTMENT - PUSH n’ LEARN (PnL)

Load Selection Procedure

A configuration button (Config) allows access to our 

patented Push n’ Learn™ technology to change binding 

relationships between sensors, switches and loads .

Step 1: Enter Push n’ Learn

 

Press and hold the Config button 

(on any DLM device) for 3 seconds. 

 

 

The red LED on the LMRC‑102 

begins to blink as does the red 

LED on ALL other communicating 

devices connected to the DLM Local 

Network . 

 

The red LEDs continue to blink until you exit PnL mode .

 

All loads in the room turn OFF immediately after 

entering PnL, then one load will turn ON . This is Load 

#1, which is bound to switch button #1 and occupancy 

sensors as part of the  Plug n’ Go factory default setting . 

All switch buttons and sensors that are bound to this 

load have their blue LED solid ON.

Step 2: Load selection

 

Press and release the Config button to step through 

the loads connected to the DLM Local Network . As 

each load turns ON note the devices (switch buttons 

and sensors) that are showing a bright solid blue LED . 

These devices are currently bound to the load that is 

ON . The blue LED on the room controller or plug load 

controller connected to the load is also lit .

•  To 

unbind

 a switch button from a load, press the 

switch button while its blue LED is ON bright . The 

blue LED goes dim to indicate the button no longer 

controls the load that is currently ON .

•  To 

unbind

 an occupancy sensor, press the up (

)

 

or 

down (

) adjustment button while its blue LED is 

ON . The blue LED turns OFF to indicate the sensor no 

longer controls the load that is currently ON . 

 

Pressing the switch or up (

)

 

or down (

) button again 

while the load is ON 

rebinds

 the load to the button or 

sensor and the blue LED illuminates brightly .

Step 3: Exit Push n’ Learn

 

Press and hold the Config button until the red LED turns 

OFF, approximately 3 seconds .

 

Load A ON/OFF button

 

Load B ON/OFF button

Blue LED ON when load is ON

0461373638

0341373638

Serial 

Number

Room

Controller

Load

Control

LMRC-102

3

4

0461373679

Master

0341373638

LMRC-102

1

2

A

B

A

B

The LMRC‑102 has 

two load relays . In a 

DLM local network with 

only LMRC‑102 room 

controllers, the LMRC‑

102 with the highest 

serial number is the 

Master, carrying Load 

1 and Load 2 . The next 

highest serial number 

would have Load 3 and 

Load 4, and so forth .

Reviews: