SPECIFICATIONS

Voltages ...............................................120 or 277VAC, 50/60Hz
Load Requirements
 

@120VAC, 50/60Hz ...........0-1300W ballast & incandescent

 

@277VAC, 50/60Hz .....................................0-3000W ballast

Santa Clara, CA 95050

Summary of Contents for InteliSwitch AS-100

Page 1: ...tions InteliSwitch AS 100 Automatic Control Switch 120 277VAC SPECIFICATIONS Voltages 120 or 277VAC 50 60Hz Load Requirements 120VAC 50 60Hz 0 1300W ballast incandescent 277VAC 50 60Hz 0 3000W ballast Santa Clara CA 95050 ...

Page 2: ...can also send a shut OFF signal to warn users that the switch will shut OFF lighting in five minutes The LED on the AS 100 will blink and an audible beep if enabled see SETUP section warns users of the impending shut OFF The display has three 3 LEDs that indicate activity and Setup Mode options or current choices The center red LED blinks during the shut OFF time delay indicating that lights will s...

Page 3: ...Only 2 Attach the switch to the wall by mounting it in the wall box with the two 2 mounting screws provided 3 Install the cover plate 4 Turn ON power to the switch and if necessary put it into Setup Mode to select options WARNING TURN POWER OFF AT CIRCUIT BREAKER BEFORE INSTALLING SWITCH www wattstopper com ...

Page 4: ...d Lighting Control Panel Line Ground Signal Only No connection for this application Line Ground Load 3 Way Line Ground Ground Signal Only Do not connect to line voltage Line Ground Load 3 Way Line Ground Load 3 Way Hot Lighting Control Panel Line Remote Switch Master Switch No Load Connection Load Neutral Signal Only Do not connect to line voltage Wiring a single switch to a lighting control panel...

Page 5: ...e option selections until the desired options are displayed 3 To exit Setup Mode and save the selected options Press and hold the ON OFF button until the LEDs flash every second from right to left approximately 3 seconds If the lights controlled by this switch are ON the lighting fixtures will turn OFF Setup is now complete and the option selections are saved If the ON OFF button is not pressed to e...

Page 6: ...Interrupt Duration Automatic ON 3 sec Lights turn ON if Automatic ON Setup Mode option is enabled Automatic OFF 5 sec Lights turn OFF when power is interrupted for 5 seconds turn back ON for 7 seconds then turn OFF Automatic Delayed OFF 1 2 sec Initiates a five minute delay period before shutting OFF lights At any time pushing the ON OFF button before the lights turn OFF cancels the countdown and k...

Page 7: ...n choosing automatic commands to delay OFF shut OFF or turn ON the switch by interrupting power to the switch check the specified time duration and make sure the resolution for timing is one quarter of a second see Operation section 5 Check to make sure that the ground terminal is connected The AS 100 will not operate properly without a ground connection 6 If the AS 100 is still not functioning pro...

Page 8: ...95050 Technical Support 800 879 8585 www wattstopper com 01862r6 7 2008 Please Recycle ORDERING INFORMATION Catalog Description AS 100 Automatic Control Switch ASP 211 Cover plate for single gang box one included with each switch ASP 422 Blank cover plate for double gang box ASP 432 Cover plate for double gang box with switch option W for white I for ivory A for light almond Cover Plates The Watt ...