LENS OPTIONS
Several lenses are available for use with the FSP-211.
Lenses give coverage at mounting heights between 8’ - 40’
for applications such as, offices, warehouses and outdoor
use. Density and range of the coverage is determined by
the type of lens and mounting height. Lens modules are IP-
66 rated when combined with an FSP-211 sensor mounted
to an outdoor rated fixture. See the FSP-Lx Coverage Guide
for more information.
WIRING
Non-Dimming
Driver
LINE
NEUTRAL
NEUTRAL
LOAD
* GROUND
Occupancy Sensor
5E4
800.879.8585
www.wattstopper.com
15195r
1
LO
AD
LINE
NEUT
(violet
)
(g
re
y)
18-20 AWG Solid CU Wire Only
230 VAC, 50 Hz
1200W max ballast
FSP-211
GRND
DIM-
DIM+
14-18 AWG Solid CU Wire Only
High/Low PIR
Non-Dimming Driver
Dimming
Driver
LINE
NEUTRAL
NEUTRAL
*GROUND
GRAY (-)
VIOLET (+)
LOAD
Occupancy Sensor
5E4
800.879.8585
www.wattstopper.com
15195r
1
LO
AD
LINE
NEUT
(violet
)
(g
re
y)
18-20 AWG Solid CU Wire Only
230 VAC, 50 Hz
1200W max ballast
FSP-211
GRND
DIM-
DIM+
14-18 AWG Solid CU Wire Only
High/Low PIR
Dimming Driver
FSP-211 COMMISSIONING
The commissioning process establishes the appropriate
parameters for the FSP-211 operation. This is done through
the FSIR-100 commissioning tool. If no commissioning
steps are taken, the sensor will use its default parameter
values.
USING THE FSIR-100 COMMISSIONING TOOL
T
he FSIR-100 Wireless IR Commissioning Tool is a
handheld tool for changing defaults and testing of
WattStopper FSP-211.It provides wireless access to the
FSP-211 sensors for parameter changes and testing.
The FSIR-100 display shows menus and prompts to lead
you through each process. The navigation pad provides a
simple way to navigate through the customization fields.
Within a certain mounting height of the sensor, the FSIR-
100 allows modification of the system without requiring
ladders or tools; simply with a touch of a few buttons.
The FSIR-100 IR transceiver allows bi-directional
communication between the FSP-211 and the FSIR-100
commissioning tool . Simple menu screens let you see
the current status of the sensor and make changes. It
can change FSP-211 sensor parameters such as high/
low mode, sensitivity, time delay, cut off and more. With
the FSIR-100 you can also establish and store FSP-211
parameter profiles.
BATTERIES
The FSIR-100 operates on three
standard 1.5V AAA Alkaline batteries
or three rechargeable AAA NiMH
batteries. The battery status displays
in the upper right corner of the
display. Three bars next to BAT=
indicates a full battery charge. A
warning appears on the display when
the battery level falls below a minimum acceptable level. To
conserve battery power, the FSIR-100 automatically shuts
off 10 minutes after the last key press.
• If communication is not successful, (if possible) move
closer to the sensor.
• If still not successful, there may be too much IR
interference from other sources. Programming the
unit at night when there is no daylight available may
be the only way to communicate with the sensor.
1. Determine an appropriate mounting location
inside the light fixture minimizing the electric light
contribution to the sensor’s photocell. Allow a
minimum distance of 0.2” (5.1mm) from the wiring
end of the sensor to the wall of the fixture.
2. Drill a hole 1.30” (33.0mm) in diameter through the
sheet metal in the bottom of the fixture.
3. Add the rubber gasket to the threaded collar,
and install the sensor face down, parallel to the
mounting surface. Ensure the rubber gasket
touches the inside surface of the fixture. Install the
plastic nut securely against the fixture to a torque of
25-30 in-lbs to ensure IP rating is maintained.
4. Align the locking features between the sensor and
lens module and push the lens module forward
until the o-ring seals firmly. Turn the lens module
clockwise to ensure it locks in place.
5. Connect wires as shown in wiring diagram.
6. Restore power from the circuit breaker.
CAUTION
TURN THE POWER OFF AT THE CIRCUIT BREAKER
BEFORE INSTALLING THE SENSOR.
Tightening
Nut
Tightening
Nut
Fixture
Wall
Lens Assembly
FSP-211
Outside
Fixture Wall
Inside Fixture
Wall
Rubber
Gasket
Rubber
Gasket
Note:
The Outside Fixture Wall thickness should be no greater
than 0.125” (3.18mm) for optimal sensor mounting and security.
Note:
The FSP-211 must be grounded to ensure signal
integrity, not for safety ground.
Outdoor Use at the exposed Sensor Collar part only
when installed at the specific location per Installation
Instructions with a Listed Outdoor Enclosure.
INSTALLATION
Call 800-879-8585 for Technical Support