Call 800.879.8585 for Technical Support
LIGHT LEVEL FEATURE
The Light Level feature holds lights off upon initial occupancy if adequate
ambient light exists. It will not turn the lights off if they are on. The default
setting is for maximum, meaning that even the brightest ambient light will not
hold the lights off. When the light level is set it is written to memory so that in
the event of a power failure the setting is not lost.
• Avoid mounting the sensor close to lighting fixtures.
• Adjust during daylight hours when ambient light in the area is at desired
level.
1. Open the Front Cover and locate the Light Level pushbutton. See Sensor
Adjustment.
2. Momentarily press the Light Level pushbutton. Do not exceed 4 seconds. *
The sensor enters setup mode, as indicated by the rapidly flashing Red LED.
The LED will flash throughout the setup process. Occupancy indications from
the LEDs are disabled during setup.
3. Move away from the sensor to avoid interference with light level detection.
The sensor measures the light level for a 25-second period, then averages
the readings and automatically sets the light level function.
4. When the Red LED stops flashing, replace the Front Cover.
* Pressing the pushbutton for 5 seconds or more resets the light level to the
default. The Green LED flashes rapidly for 10 seconds after the setting has
changed.
Summary of Contents for DT-355