SENSOR ADJUSTMENT

The sensors are factory preset to allow for quick installation in most applications. 
Verifi cation of proper wiring or coverage, or customizing the sensor’s settings can 
be done using the following procedures. To make adjustments, open the Front Cover 
with a small screwdriver.

There is a 30 second warm-up period 
when power is fi rst applied. 

Before making adjustments, make 
sure the offi ce furniture is installed, 
lighting circuits are turned on, and the 
HVAC systems are in the overridden/
on position. VAV systems should be 
set to their highest airfl ow. Set the 
Logic Confi guration and Time Delay 
to the desired settings. See “Logic 
Confi guration Chart”, next page.

To Test Occupancy Sensors

1.   Ensure the PIR and Ultrasonic 

Activity LEDs are enabled (DIP 
switch 7 ON) and PIR Sensitivity is 
set to MAX (DIP switch #8 ON).

2.  Ensure the Time Delay is set for 

Test Mode*

 using the “5 seconds/Auto” setting. 

(DIP switches 4, 5, & 6 are OFF). 

3.   Ensure that the Light Level is at default (maximum). 

4.   Ensure that the Ultrasonic Sensitivity trimpot is set to about 90%, clockwise.

5.   Remain still. The red and green LEDs should not fl ash. The lights should turn off 

after 5 seconds. (If not, see “Troubleshooting.”)

6.   Move about the coverage area. The lights should come on. Adjust the Ultrasonic 

Sensitivity as necessary to provide the desired coverage (Green LED indicates 
activation from the ultrasonic sensor).

When testing and adjustment is complete, reset DIP Switches and Light Level to the 
desired settings, and replace the cover on the sensor.

If you need to invoke the 

Test Mode

 and the DIP switches are already set for 

5 seconds/Auto, toggle DIP switch #5 ON then back to the OFF position.  This 
provides a 5 minute test period. During the test period, the Time Delay is only 5 
seconds.

PIR Lens

Photocell

Ultrasonic 
Transducer 
Cones

PIR 
Activity LED

Ultrasonic 
Activity LED

Front Cover

Adjustments under the front cover

Press for Auto set
Hold 5 sec to disable 

Light Level
Button

Min

      

Max

Sensitivity

DIP

Switch

See

Back

Call 800.879.8585 for Technical Support

Summary of Contents for DT-200

Page 1: ...F 0 to 55 C Light Level One Step Adjustment 10FC to 300FC Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec upon intial power up or DIP switch reset PIR Coverage Typical 1000 ft2 Sensitivity Adjustment Automatic or Low DIP switch setting Ultrasonic Coverage Typical 800 1200 ft2 Sensitivity Adjustment Minimum to Maximum trimpot Frequency 4...

Page 2: ... 5 to 30 minutes the lights are switched off A walk through mode can turn lights off after only 3 minutes if no activity is detected after 30 seconds of an occupancy detection The DT 200 operates on 24VDC supplied by WattStopper Power Packs DT 200 sensors also have an isolated relay with Normally Open and Normally Closed contacts for interfacing with HVAC or EMS COVERAGE PATTERN The DT 200 provide...

Page 3: ...verage patterns As a general rule each occupant should be able to clearly view the sensor Masking the PIR Lens Opaque adhesive tape is supplied so that sections of the PIR lens can be masked This restricts the sensor s view and allows you to eliminate PIR coverage in unwanted areas such as hallways outside of the desired coverage area Since masking removes bands of coverage remember to take this i...

Page 4: ...om power pack to the yellow wire on the sensor To add a MOMENTARY MANUAL SWITCH such as the LVS 1 Momentary Toggle Switch to the above applications connect Wire from one side of switch to the green wire on sensor Wire from other side of switch to the gray wire on sensor Wiring the ISOLATED RELAY The Isolated Relay is rated for 1A 30VAC VDC Connect the wires necessary to the application that requir...

Page 5: ...ontact Orange Normally Open Contact Red Common Isolated Relay Outputs Blue Light Level Green Common DT 200v2 Occupancy Sensor Green wire on sensor is only used when connecting a manual momentary switch LVS 1 Load Blue Control Out Black 24V Low Voltage Class 2 Line Voltage Line Neutral Feed Through Power Pack Man Switch Red Common Man Switch Common Jumper Back of LVS 1 Ceiling DT 200v2 Occupancy Se...

Page 6: ...acket so that it is in line with the half circle notch as illustrated in figure A Push the ball into the Base Bracket opening until it snaps into place being careful not to pinch the wires The brackets can be easily connected or disconnected using this orientation 5 Insert the Tightening Screw and Nut into the Base Bracket as illustrated 6 Use the Reference Surface Angle to adjust the sensor for op...

Page 7: ...ning Screw to hold this position Wall Mount PARALLEL to WALL at 10 foot mounting height Reference Surface Angle Ceiling Mount PARALLEL to VERTICAL at 10 foot mounting height Reference Surface Angle fig C Override To override all sensor functions set the Ultrasonic Sensitivity trimpot to the fully counterclockwise Override position This bypasses the occupancy control functions of the sensor but stil...

Page 8: ... 5 6 are OFF 3 Ensure that the Light Level is at default maximum 4 Ensure that the Ultrasonic Sensitivity trimpot is set to about 90 clockwise 5 Remain still The red and green LEDs should not flash The lights should turn off after 5 seconds If not see Troubleshooting 6 Move about the coverage area The lights should come on Adjust the Ultrasonic Sensitivity as necessary to provide the desired covera...

Page 9: ...n starts when no motion is detected After no motion is detected for the length of the time delay the sensor will turn the lights off The sensor can select the time delay using the Auto setting or you can select a fixed time delay Auto records occupancy patterns and uses this history to choose an optimal time delay from 5 to 30 minutes Recording starts immediately and optimization is continuous as h...

Page 10: ... manual switch must be used to turn the load on if there is no movement detected within the 30 second re trigger period Automatic ON Mode any Trigger Option except 6 or 7 These options use occupancy triggers as well as switch activation to turn the load ON A manual switch provides the following additional functionality a The load can be turned ON by manual switch activation and it stays on accordi...

Page 11: ...led area To test whether the Light Level adjustment is the problem cover the area around the green LED see diagram with your hand to see if the lights turn on If the lights turn on the Light Level setting was keeping the lights off see Sensor Adjustment for readjustment 2 Check all sensor and power pack wire connections 3 Check for 24VDC at the power pack s blue wire connection to sensor while sen...

Page 12: ...ssible solutions 1 Reduce the ultrasonic sensitivity as needed see Sensor Adjustment 2 Mask the lens to reduce PIR coverage see Masking the PIR Lens under Placement Guidelines 3 Change the logic configuration setting see DIP Switches 4 Relocate the sensor Catalog Description DT 200 Dual Technology Occupancy Sensor Low Voltage w Isolated Relay DT 205 Dual Technology Occupancy Sensor Low Voltage BZ 1...