REPLAcING UV LAMP AND SERVIcING UV SYSTEM

NOTE: Avoid touching the sides of the quartz sleeve and lamp, handle by the ends only.

Step 1

Disconnect power.

Step 2

Turn water off and open valve down stream of system to relieve pressure.

Step 3

Remove vinyl cap and unscrew the nut.

Step 4

Carefully withdraw lamp approximately 2 inches from chamber.

Step 5

While holding lamp end carefully remove lamp socket on end now exposed.

Sept 6

Carefully withdraw lamp from chamber.

Step 7

Carefully remove O-ring from the end of quartz sleeve.

Step 8

Carefully remove quartz sleeve.

Step 9

To reinstall follow steps 8 through 1 in reverse.

MAINTENANcE SUGGESTION

To operate the sterilizer properly and attain its maximum efficiency it is recommended that the user performs the following maintenance:

1.  Quartz sleeve cleaning or replacement:

a. Quartz sleeve is to be cleaned every 6 -12 months. Clean with glass cleaner.
b. Quartz sleeve is to be replaced every 24 months.

2.  UV lamp replacement is recommended every 8000 - 9000 hours or operation (approx. 12 months of continuous service).

cAUTION:

Ultraviolet lamp and quartz sleeve are easily damaged. Pay attention when removing or replacing lamp and quartz sleeve!

ASSEMBLY

:

WARNING:

Germicidal ultraviolet rays are harmful to eyes and skin.

ITEM

DEScRIPTION

PART NUMBER

1

Ballast Assembly

WUVBALLAST2 (or 6, 8, 12) available in 110V or 230V

2

Germicidal Ultraviolet Lamp WUVLAMP2 (or 6, 8, 12)

3

Rubber O-Ring

T1200-0116

4

Quartz Sleeve

WUVQS2 (or 6,8,12)

5

Chamber

N/A

6

Mounting Clip

C2500W