3.3 DIP switch configuration
DIP switch number Function
Value
(default: OFF)
Configuration
Description
DIP1
Controller function
OFF
Main Controller
See 4.3
ON
Sub Controller
DIP2*
Pump (available only on
main controller, the sub
is always local)
OFF
Local pump
See 4.5
ON
Global pump
DIP3
Pump start delays
OFF
2min
See 4.5
ON
5min
DIP4*
H&C Order
OFF
External H&C input
See 4.4
ON
Master Thermostat
DIP5*
Time before H&C switch
OFF
No delay
See 4.6
ON
5 minutes delay
DIP6
H&C outputs
OFF
Demand on any zone
See 4.6
ON
Mode
DIP7
Not used
DIP8
Not used
*Available only on main controller (dip switch 1 => OFF)
ON
OFF
DIP8
DIP7
DIP6
DIP5
DIP4
DIP3
DIP2
DIP1
Operate the dip switch when the product is powered off.