Installation Instructions:

1.Check that the valve is suitable for the application.
2. Valve must be fitted by a qualified plumber.
3. Installation must comply with local authority requirements.
4. Valve may be installed in any orientation.
5. Flush pipes prior to fitting.
6. Connections are H (hot inlet), C (cold inlet) and OUT (mixed temperature outlet).
7. Do NOT apply heat near valve during installation – this may damage the   
     mechanism.
8. Do NOT install valve directly into outlet of cylinder.
9. At the end of the installation, check thoroughly that it is installed correctly.
10. Adjust temperature by removing cap. Use screwdriver to adjust to desired  
      temperature. To increase, turn anti-clockwise (H). To decrease, turn clockwise  
      (C). Replace cap. Maximum delivered hot water temperature at any sanitary  
      fixture used for personal hygiene shall not exceed 50°C.
11. Maintenance is to be carried out to AS 4032.3
12. Commissioning: All valves must be commissioned and the discharge water  
       temperature set and verified with a thermometer. Valves not installed in  
       accordance to these instructions may result in unsafe performance.
13. Refer to diagram on other side for installation