background image

2

Reduced Pressure Zone Backflow Preventers must be 

inspected and tested periodically, 

in accordance with local codes, to ensure proper operation of 

check valves within the unit. A differential pressure gauge is 

recommended for Test No. 1 rather than a manometer for the 

following reasons: It utilizes minimum time to perform the test. 

It eliminates the necessity of closing the inlet ball valve which 

could release pipe scale and foreign matter into the backflow 

preventer. Only a slight amount of water is ‘spilled’ in test. A 

mercury manometer could cause a pollution hazard.

Test Set Up

Reduced Pressure Zone Assembly

Close Valves A, B and C on Test Kit.
Connect high side hose to test cock #2
Connect low side hose to test cock #3. Close shutoff #2.
Open test cocks #2 and #3.
Open vent valve C.
Open ‘high’ valve A and bleed to atmosphere until all the air  

is expelled.
Close valve A. Open ‘low’ valve B and bleed to atmosphere until 

all air is expelled. Close ‘low’ valve B. Close ‘vent’ valve C.
Connect vent hose to test cock #4.

Test Procedure

Reduced Pressure Zone Assembly
Field Test Equipment Required
Reduced Pressure Zone Backflow Preventer Test Kit

Test No. 1

Purpose:

 To test check valve No. 2 for tightness against re-

verse flow.

Requirements:

 Valve must be tight against reverse flow under 

all pressure differentials. Slowly open the 

high

 valve A and 

the 

vent

 valve C, and keep the 

low

 valve B closed. Open test 

cock #4. Indicated pressure differential will decrease slightly. If 

pressure differential continues to decrease (until the vent opens) 

check valve #2 is reported as 

leaking

.

Test No. 2

Purpose:

 To test shutoff #2 for tightness.

Requirements:

 After passing Test No. 1, continue to Test No. 

2 by closing test cock #2. The indicated pressure differential will 

decrease slightly. If pressure differential continues to decrease 

(approaching “zero”), shutoff #2 is reported to be “leaking”.

Test No. 3

Purpose:

 To test Check Valve No. 1 for tightness.

Requirements:

 Valve must be tight against reverse flow under 

all pressure differentials. Close 

high

 valve A and open test cock 

#2. Close test cock #4. Disconnect vent hose at test cock #4. 

Open valves B and C, bleeding to atmosphere. Then closing 

valve B restores the system to a normal static condition. Ob-

serve the pressure differential gauge. If there is a decrease in the 

indicated value, Check Valve No. 1 is reported as “leaking”.

Test No. 4

Purpose:

 To test operation of pressure differential relief valve.

Requirements:

 The pressure differential relief valve must 

operate to maintain the “zone” between the two check valves 

at least 2 psi less than the supply pressure. Close 

vent

 valve 

C. Open 

high

 valve A. Open the 

low

 valve B very slowly until 

the differential gauge needle starts to drop. Hold the valve at 

this position and observe the gauge reading at the moment the 

first discharge is noted from the relief valve. Record this as the 

opening differential pressure of the relief valve.

NOTICE

It is important that the differential gauge needle drops slowly. 
Close test cocks #2 and #3. Use 

vent

 hose to relieve pressure 

from test kit by opening valves A, B and C. Remove all test 

equipment and open shutoff #2.

Ball Type  

Test Valves

(A)

(C)

(B)

Needle 

Valve

Auxiliary 

Test Cock

High Hose

(Color - Yellow)

Low Hose 

(Color - White or Red)

Vent Hose

(Color - Blue)

Test Cock 

No. 1

Test Cock 

No. 2

Test Cock 

No. 3

Test Cock 

No. 4

Shutoff 

No. 1

Check Valve 

No. 2

Shutoff 

No. 2

Check Valve 

No. 1

909QT shown

CAUTION

!

To prevent freezing, hold Test Kit vertically to drain 
differential gauge and hoses prior to placing in case.

No. TK-9 Model “A” Test Kit

Summary of Contents for TK-9A

Page 1: ...ce dual scale 0 15 psid and 0 1 kg cm2 2 accuracy full scale Test Valves 2 ball valves and 1 needle valve Hoses 3 3 with female threaded swivel couplings Adaptors 3 1 4 threaded coupling adaptors 3 1 2 x 1 4 bushings 3 3 4 x 1 4 bushings 1 16 securing strap 1 Moisture resistant instruction guide Case light weight shock resistant molded plastic with foam inserts WARNING This product contains chemic...

Page 2: ...e to Test No 2 by closing test cock 2 The indicated pressure differential will decrease slightly If pressure differential continues to decrease approaching zero shutoff 2 is reported to be leaking Test No 3 Purpose To test Check Valve No 1 for tightness Requirements Valve must be tight against reverse flow under all pressure differentials Close high valve A and open test cock 2 Close test cock 4 D...

Page 3: ...re Differential Relief Valve Pressure Differential Relief Valve Pressure Differential Relief Valve Gate Valve Shutoff No 1 Gate Valve Shutoff No 2 Test cock No 3 Test cock No 4 Test cock No 1 Test cock No 2 Air Vent Test cock No 3 Test cock No 4 Shutoff No 1 Test cock No 2 Shutoff No 2 Test cock No 1 Series 009 LF009 Reduced Pressure Zone Backflow Preventer 1 4 to 2 Series 909 LF909 Reduced Pressu...

Page 4: ...est Cock No 4 Test Cock No 1 Test Cock No 2 709NRS Shown 1 007 shown IS TK 9A 1323 EDP 0834222 2013 Watts USA Tel 978 688 1811 Fax 978 794 1848 www watts com Canada Tel 905 332 4090 Fax 905 332 7068 www watts ca Limited Warranty Watts Regulator Co the Company warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of origi...

Reviews: