background image

3

Install the Flood Sensor and Activation Module

The activation module receives a signal from the flood sensor when a discharge is detected.  

If the discharge meets the conditions of a qualifying event, the normally open contact is closed to 

provide a signal to the BMS input terminal.
The flood sensor and assembly shown in the installation sequence are representative only. Each flood 

sensor is designed specifically for the assembly to which it is attached.

Custom Flood Sensor Settings 

The default settings on the activation module for detecting discharge are suitable for 

the assembly series. However, the DIP switches can customized for a different wet 

threshold and time delay. Scan the QR code for more information.

1.  Remove the dust cover from the sensor.

2.  Press the activation module onto the sensor.

3.  Check that the module is fully seated to seal the O-ring and 

to make electrical contact.

NOTICE

Retain the dust cover to protect the flood sensor when the 

activation module needs to be removed or replaced.

Summary of Contents for SentryPlus Alert Series

Page 1: ...us Alert technology does not replace the need to comply with all required instructions codes and regu lations related to the installation operation and maintenance of the backflow preventer to which i...

Page 2: ...od sensors compatible with this kit refer to ordering code 88009418 FP BF BMS at watts com A Activation module with 8 conductor cable and ground wire B 24V DC power adapter NOTICE When installing an a...

Page 3: ...ecifically for the assembly to which it is attached Custom Flood Sensor Settings The default settings on the activation module for detecting discharge are suitable for the assembly series However the...

Page 4: ...usage for a period of one year from the date of original shipment In the event of such defects within the warranty period the Company will at its option replace or recondition the product without char...

Page 5: ...entryPlus Alert ne remplace pas la n cessit de se conformer toutes les instructions tous les codes et tous les r glements requis li s l installation au fonctionnement et l entretien de l appareil anti...

Page 6: ...sultez le code de commande 88009418 FP BF BMS sur watts com A Module d activation avec c ble conducteur de 8 pieds 2 4 m tres et fil de mise la terre B Adaptateur d alimentation 24 V CC Lors d une ins...

Page 7: ...st fix R glages personnalis s du d tecteur d inondation Les r glages par d faut sur le module d activation pour la d tection d vacuation conviennent la s rie de l assemblage Cependant les commutateurs...

Page 8: ...ode d un an compter de la date d exp dition d origine Si une telle d faillance devait se produire au cours de la p riode sous garantie la Soci t pourra sa discr tion remplacer le produit ou le remettr...

Page 9: ...con todas las instrucciones la normas y los reglamentos necesarios relacionados con la insta laci n la operaci n y el mantenimiento del dispositivo de prevenci n de contraflujo al que est conectado in...

Page 10: ...on este kit consulte el c digo de pedido 88009418 FP BF BMS en watts com A M dulo de activaci n con cable conductor de 8 pies 2 44 m y cable de conexi n a tierr B Adaptador de alimentaci n de 24 V AVI...

Page 11: ...st conectado Configuraci n personalizada del sensor de inundaci n Los ajustes predeterminados del m dulo de activaci n para detectar descargas son adecuados para la serie de montaje Sin embargo los in...

Page 12: ...de obra cuando se usen de forma normal durante un periodo de un a o a partir de la fecha de env o original En caso de que tales defectos se presenten dentro del per odo de garant a la Compa a a su dis...

Reviews: